| A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The affected device offered SNMP read and write capacities with a publicly know hardcoded community string. The security vulnerability could be exploited by an attacker with network access to the affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. |
| A vulnerability has been identified in SIEMENS LOGO!8 (6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware version V1.80.xx and V1.81.xx), SIEMENS LOGO!8 (6ED1052-xyy08-0BA0 FS:01 / Firmware version < V1.82.02). An attacker with network access to port 10005/tcp of the LOGO! device could cause a Denial-of-Service condition by sending specially crafted packets. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected service. No user interaction is required to exploit this security vulnerability. Successful exploitation of the security vulnerability compromises availability of the targeted system. At the time of advisory publication no public exploitation of this security vulnerability was known. |
| A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V2.0). Due to insufficient checking of user permissions, an attacker may access URLs that require special authorization. An attacker must have access to a low privileged account in order to exploit the vulnerability. |
| The monitor barrier of the affected products insufficiently blocks data from being forwarded over the mirror port into the mirrored network. An attacker could use this behavior to transmit malicious packets to systems in the mirrored network, possibly influencing their configuration and runtime behavior. |
| The webserver of the affected devices contains a vulnerability that may lead to
a denial of service condition. An attacker may cause a denial of service
situation which leads to a restart of the webserver of the affected device.
The security vulnerability could be exploited by an attacker with network
access to the affected systems. Successful exploitation requires no system
privileges and no user interaction. An attacker could use the vulnerability
to compromise availability of the device. |
| A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (All Versions < V5.2.4), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.5.0), SCALANCE X-300 switch family (incl. X408 and SIPLUS NET variants) (All versions < V4.1.3), SCALANCE X-414-3E (All versions). The affected devices store passwords in a recoverable format. An attacker may extract and recover device passwords from the device configuration. Successful exploitation requires access to a device configuration backup and impacts confidentiality of the stored passwords. |
| GE Communicator, all versions prior to 4.0.517, allows a non-administrative user to replace the uninstaller with a malicious version, which could allow an attacker to gain administrator privileges to the system. |
| Moxa IKS and EDS fails to properly validate user input, giving unauthenticated and authenticated attackers the ability to perform XSS attacks, which may be used to send a malicious script. |
| GE Communicator, all versions prior to 4.0.517, allows a non-administrative user to place malicious files within the installer file directory, which may allow an attacker to gain administrative privileges on a system during installation or upgrade. |
| Moxa IKS and EDS generate a predictable cookie calculated with an MD5 hash, allowing an attacker to capture the administrator's password, which could lead to a full compromise of the device. |
| In Philips Tasy EMR, Tasy EMR Versions 3.02.1744 and prior, the software incorrectly neutralizes user-controllable input before it is placed in output that is used as a web page that is served to other users. |
| Cross-site request forgery has been identified in Moxa IKS and EDS, which may allow for the execution of unauthorized actions on the device. |
| In Auto-Maskin RP210E Versions 3.7 and prior, DCU210E Versions 3.7 and prior and Marine Observer Pro (Android App), the software contains a mechanism for users to recover or change their passwords without knowing the original password, but the mechanism is weak. |
| Moxa IKS and EDS allow remote authenticated users to cause a denial of service via a specially crafted packet, which may cause the switch to crash. |
| In Auto-Maskin RP210E Versions 3.7 and prior, DCU210E Versions 3.7 and prior and Marine Observer Pro (Android App), the software contains a mechanism for users to recover or change their passwords without knowing the original password, but the mechanism is weak. |
| Several buffer overflow vulnerabilities have been identified in Moxa IKS and EDS, which may allow remote code execution. |
| When processing project files, the application (Omron CX-Programmer v9.70 and prior and Common Components January 2019 and prior) fails to check if it is referencing freed memory. An attacker could use a specially crafted project file to exploit and execute code under the privileges of the application. |
| Cscape, 9.80 SP4 and prior. An improper input validation vulnerability may be exploited by processing specially crafted POC files. This may allow an attacker to read confidential information and remotely execute arbitrary code. |
| Advantech WebAccess/SCADA, Versions 8.3.5 and prior. An improper access control vulnerability may allow an attacker to cause a denial-of-service condition. |
| A vulnerability was found in Rockwell Automation RSLinx Classic versions 4.10.00 and prior. An input validation issue in a .dll file of RSLinx Classic where the data in a Forward Open service request is passed to a fixed size buffer, allowing an attacker to exploit a stack-based buffer overflow condition. |