Filtered by vendor Schneider-electric
Subscriptions
Filtered by product Ecostruxure Control Expert
Subscriptions
Total
23 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2023-27976 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2024-11-21 | 8.8 High |
A CWE-668: Exposure of Resource to Wrong Sphere vulnerability exists that could cause remote code execution when a valid user visits a malicious link provided through the web endpoints. Affected Products: EcoStruxure Control Expert (V15.1 and above) | ||||
CVE-2023-1548 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2024-11-21 | 5.5 Medium |
A CWE-269: Improper Privilege Management vulnerability exists that could cause a local user to perform a denial of service through the console server service that is part of EcoStruxure Control Expert. Affected Products: EcoStruxure Control Expert (V15.1 and above) | ||||
CVE-2022-45789 | 1 Schneider-electric | 72 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 69 more | 2024-11-21 | 8.1 High |
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions) | ||||
CVE-2022-45788 | 1 Schneider-electric | 108 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 105 more | 2024-11-21 | 7.5 High |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions) | ||||
CVE-2022-37302 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2024-11-21 | 5.5 Medium |
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause a crash of the Control Expert software when an incorrect project file is opened. Affected Products: EcoStruxure Control Expert(V15.1 HF001 and prior). | ||||
CVE-2022-37300 | 1 Schneider-electric | 70 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 67 more | 2024-11-21 | 9.8 Critical |
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbers BMXP34*) (V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*) (V3.20 and prior). | ||||
CVE-2022-26507 | 2 Att, Schneider-electric | 9 Xmill, Ecostruxure Control Expert, Ecostruxure Process Expert and 6 more | 2024-11-21 | 9.8 Critical |
A heap-based buffer overflow exists in XML Decompression DecodeTreeBlock in AT&T Labs Xmill 0.7. A crafted input file can lead to remote code execution. This is not the same as any of: CVE-2021-21810, CVE-2021-21811, CVE-2021-21812, CVE-2021-21815, CVE-2021-21825, CVE-2021-21826, CVE-2021-21828, CVE-2021-21829, or CVE-2021-21830. NOTE: This vulnerability only affects products that are no longer supported by the maintainer | ||||
CVE-2022-24323 | 1 Schneider-electric | 2 Ecostruxure Control Expert, Ecostruxure Process Expert | 2024-11-21 | 5.3 Medium |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software, when an attacker is able to intercept and manipulate specific Modbus response data. Affected Product: EcoStruxure Process Expert (V2021 and prior), EcoStruxure Control Expert (V15.0 SP1 and prior) | ||||
CVE-2022-24322 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2024-11-21 | 5.3 Medium |
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software when an attacker is able to intercept and manipulate specific Modbus response data. Affected Product: EcoStruxure Control Expert (V15.0 SP1 and prior) | ||||
CVE-2021-22797 | 1 Schneider-electric | 8 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect and 5 more | 2024-11-21 | 7.8 High |
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal) vulnerability exists that could cause malicious script to be deployed in an unauthorized location and may result in code execution on the engineering workstation when a malicious project file is loaded in the engineering software. Affected Product: EcoStruxure Control Expert (V15.0 SP1 and prior, including former Unity Pro), EcoStruxure Process Expert (2020 and prior, including former HDCS), SCADAPack RemoteConnect for x70 (All versions) | ||||
CVE-2021-22782 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2024-11-21 | 5.5 Medium |
Missing Encryption of Sensitive Data vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause an information leak allowing disclosure of network and process information, credentials or intellectual property when an attacker can access a project file. | ||||
CVE-2021-22781 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2024-11-21 | 5.5 Medium |
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause a leak of SMTP credential used for mailbox authentication when an attacker can access a project file. | ||||
CVE-2021-22780 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2024-11-21 | 7.1 High |
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause unauthorized access to a project file protected by a password when this file is shared with untrusted sources. An attacker may bypass the password protection and be able to view and modify a project file. | ||||
CVE-2021-22779 | 1 Schneider-electric | 61 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 58 more | 2024-11-21 | 9.1 Critical |
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller. | ||||
CVE-2021-22778 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2024-11-21 | 7.1 High |
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause protected derived function blocks to be read or modified by unauthorized users when accessing a project file. | ||||
CVE-2020-7560 | 1 Schneider-electric | 2 Ecostruxure Control Expert, Unity Pro | 2024-11-21 | 8.6 High |
A CWE-123: Write-what-where Condition vulnerability exists in EcoStruxure™ Control Expert (all versions) and Unity Pro (former name of EcoStruxure™ Control Expert) (all versions), that could cause a crash of the software or unexpected code execution when opening a malicious file in EcoStruxure™ Control Expert software. | ||||
CVE-2020-7559 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2024-11-21 | 7.5 High |
A CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause a crash of the PLC simulator present in EcoStruxureª Control Expert software when receiving a specially crafted request over Modbus. | ||||
CVE-2020-7538 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2024-11-21 | 7.5 High |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause a crash of the PLC simulator present in EcoStruxureª Control Expert software when receiving a specially crafted request over Modbus. | ||||
CVE-2020-7475 | 1 Schneider-electric | 6 Ecostruxure Control Expert, Modicon M340, Modicon M340 Firmware and 3 more | 2024-11-21 | 9.8 Critical |
A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection'), reflective DLL, vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20), Modicon M580 (all versions prior to V3.10), which, if exploited, could allow attackers to transfer malicious code to the controller. | ||||
CVE-2020-28213 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2024-11-21 | 8.8 High |
A CWE-494: Download of Code Without Integrity Check vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause unauthorized command execution when sending specially crafted requests over Modbus. |