        | A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3 UC04), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC WinCC V15 and earlier (All versions < V15 SP1 Update 7), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 19), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 5). The affected systems store sensitive information in log files. An attacker with access to the log files could publicly expose the information or reuse it to develop further attacks on the system. | 
    
    
    
        | A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC WinCC V15 and earlier (All versions < V15 SP1 Update 7), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V17 (All versions <= V17 Update 4), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 19), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 6). The affected component stores the credentials of a local system account in a potentially publicly accessible project file using an outdated cipher algorithm. An attacker may use this to brute force the credentials and take over the system. | 
    
    
    
        | A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC WinCC V15 and earlier (All versions < V15 SP1 Update 7), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 19), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 6). The password hash of a local user account in the remote server could be granted via public API to a user on the affected system. An authenticated attacker could brute force the password hash and use it to login to the server. | 
    
    
    
        | A vulnerability has been identified in OpenPCS 7 V8.2 (All versions), OpenPCS 7 V9.0 (All versions < V9.0 Upd4), OpenPCS 7 V9.1 (All versions), SIMATIC BATCH V8.2 (All versions), SIMATIC BATCH V9.0 (All versions), SIMATIC BATCH V9.1 (All versions), SIMATIC NET PC Software V14 (All versions), SIMATIC NET PC Software V15 (All versions), SIMATIC NET PC Software V16 (All versions < V16 Update 6), SIMATIC NET PC Software V17 (All versions < V17 SP1), SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3 UC04), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC Route Control V8.2 (All versions), SIMATIC Route Control V9.0 (All versions), SIMATIC Route Control V9.1 (All versions), SIMATIC WinCC V15 and earlier (All versions < V15 SP1 Update 7), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 19), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 5). When downloading files, the affected systems do not properly neutralize special elements within the pathname. An attacker could then cause the pathname to resolve to a location outside of the restricted directory on the server and read unexpected critical files. | 
    
    
    
        | A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3 UC04), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC WinCC V15 and earlier (All versions < V15 SP1 Update 7), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 19), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 5). Legitimate file operations on the web server of the affected systems do not properly neutralize special elements within the pathname. An attacker could then cause the pathname to resolve to a location outside of the restricted directory on the server and read, write or delete unexpected critical files. | 
    
    
    
        | In OPC Foundation Local Discovery Server (LDS) before 1.04.402.463, remote attackers can cause a denial of service (DoS) by sending carefully crafted messages that lead to Access of a Memory Location After the End of a Buffer. | 
    
    
    
        | An OpenSSL TLS server may crash if sent a maliciously crafted renegotiation ClientHello message from a client. If a TLSv1.2 renegotiation ClientHello omits the signature_algorithms extension (where it was present in the initial ClientHello), but includes a signature_algorithms_cert extension then a NULL pointer dereference will result, leading to a crash and a denial of service attack. A server is only vulnerable if it has TLSv1.2 and renegotiation enabled (which is the default configuration). OpenSSL TLS clients are not impacted by this issue. All OpenSSL 1.1.1 versions are affected by this issue. Users of these versions should upgrade to OpenSSL 1.1.1k. OpenSSL 1.0.2 is not impacted by this issue. Fixed in OpenSSL 1.1.1k (Affected 1.1.1-1.1.1j). | 
    
    
    
        | A vulnerability has been identified in LOGO! CMR2020 (All versions < V2.2), LOGO! CMR2040 (All versions < V2.2), SIMATIC RTU3010C (All versions < V4.0.9), SIMATIC RTU3030C (All versions < V4.0.9), SIMATIC RTU3031C (All versions < V4.0.9), SIMATIC RTU3041C (All versions < V4.0.9). The underlying TCP/IP stack does not properly calculate the random numbers used as ISN (Initial Sequence Numbers). An adjacent attacker with network access to the LAN interface could interfere with traffic, spoof the connection and gain access to sensitive information. | 
    
    
    
        | A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (V4.5.0). Affected devices fail to authenticate against configured passwords when provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC. The vulnerability does not occur when TIA Portal V13 SP1 or any later version was used to provision the device. | 
    
    
    
        | A vulnerability has been identified in SIMATIC CP 343-1 (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 Advanced (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 ERPC (All versions), SIMATIC CP 343-1 Lean (incl. SIPLUS variants) (All versions), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 Advanced (All versions < V3.3), SIPLUS NET CP 443-1 (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (All versions < V3.3). Sending a specially crafted packet to port 102/tcp of an affected device could cause a denial of service condition. A restart is needed to restore normal operations. | 
    
    
    
        | A vulnerability has been identified in SIMATIC CP 1543-1 (incl. SIPLUS variants) (All versions < V3.0), SIMATIC CP 1545-1 (All versions < V1.1). An attacker with access to the subnet of the affected device could retrieve sensitive information stored in cleartext. | 
    
    
    
        | An issue was discovered in Insyde InsydeH2O Kernel 5.0 before 05.09.11, 5.1 before 05.17.11, 5.2 before 05.27.11, 5.3 before 05.36.11, 5.4 before 05.44.11, and 5.5 before 05.52.11 affecting FwBlockServiceSmm. Software SMI services that use the Communicate() function of the EFI_SMM_COMMUNICATION_PROTOCOL do not check whether the address of the buffer is valid, which allows use of SMRAM, MMIO, or OS kernel addresses. | 
    
    
    
        | A vulnerability exists in SMM (System Management Mode) branch that registers a SWSMI handler that does not sufficiently check or validate the allocated buffer pointer(QWORD values for CommBuffer). This can be used by an attacker to corrupt data in SMRAM memory and even lead to arbitrary code execution. | 
    
    
    
        | An issue was discovered in Kernel 5.x in Insyde InsydeH2O, affecting HddPassword. Software SMI services that use the Communicate() function of the EFI_SMM_COMMUNICATION_PROTOCOL do not check whether the address of the buffer is valid, which allows use of SMRAM, MMIO, or OS kernel addresses. | 
    
    
    
        | A vulnerability has been identified in SIMATIC PCS 7 V8.2 and earlier (All versions), SIMATIC PCS 7 V9.X (All versions < V9.1 SP2), SIMATIC PDM (All versions < V9.2 SP2), SIMATIC STEP 7 V5.X (All versions < V5.7), SINAMICS STARTER (containing STEP 7 OEM version) (All versions < V5.4 SP2 HF1). A directory containing metafiles relevant to devices' configurations has write permissions. An attacker could leverage this vulnerability by changing the content of certain metafiles and subsequently manipulate parameters or behavior of devices that would be later configured by the affected software. | 
    
    
    
        | A vulnerability has been identified in SIMATIC PCS 7 V8.2 and earlier (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3), SIMATIC PDM (All versions < V9.2), SIMATIC STEP 7 V5.X (All versions < V5.6 SP2 HF3), SINAMICS STARTER (containing STEP 7 OEM version) (All versions < V5.4 HF2). The affected software contains a buffer overflow vulnerability while handling certain files that could allow a local attacker to trigger a denial-of-service condition or potentially lead to remote code execution. | 
    
    
    
        | A vulnerability has been identified in SIMATIC RF166C (All versions > V1.1 and < V1.3.2), SIMATIC RF185C (All versions > V1.1 and < V1.3.2), SIMATIC RF186C (All versions > V1.1 and < V1.3.2), SIMATIC RF186CI (All versions > V1.1 and < V1.3.2), SIMATIC RF188C (All versions > V1.1 and < V1.3.2), SIMATIC RF188CI (All versions > V1.1 and < V1.3.2), SIMATIC RF360R (All versions < V2.0), SIMATIC Reader RF610R CMIIT (All versions > V3.0 < V4.0), SIMATIC Reader RF610R ETSI (All versions > V3.0 < V4.0), SIMATIC Reader RF610R FCC (All versions > V3.0 < V4.0), SIMATIC Reader RF615R CMIIT (All versions > V3.0 < V4.0), SIMATIC Reader RF615R ETSI (All versions > V3.0 < V4.0), SIMATIC Reader RF615R FCC (All versions > V3.0 < V4.0), SIMATIC Reader RF650R ARIB (All versions > V3.0 < V4.0), SIMATIC Reader RF650R CMIIT (All versions > V3.0 < V4.0), SIMATIC Reader RF650R ETSI (All versions > V3.0 < V4.0), SIMATIC Reader RF650R FCC (All versions > V3.0 < V4.0), SIMATIC Reader RF680R ARIB (All versions > V3.0 < V4.0), SIMATIC Reader RF680R CMIIT (All versions > V3.0 < V4.0), SIMATIC Reader RF680R ETSI (All versions > V3.0 < V4.0), SIMATIC Reader RF680R FCC (All versions > V3.0 < V4.0), SIMATIC Reader RF685R ARIB (All versions > V3.0 < V4.0), SIMATIC Reader RF685R CMIIT (All versions > V3.0 < V4.0), SIMATIC Reader RF685R ETSI (All versions > V3.0 < V4.0), SIMATIC Reader RF685R FCC (All versions > V3.0 < V4.0). Affected devices do not properly handle large numbers of incoming connections. An attacker may leverage this to cause a Denial-of-Service situation. | 
    
    
    
        | An issue was discovered in Wind River VxWorks before 6.5. There is a possible heap overflow in dhcp client. | 
    
    
    
        | A vulnerability has been identified in SIMATIC Process Historian 2013 and earlier (All versions), SIMATIC Process Historian 2014 (All versions < SP3 Update 6), SIMATIC Process Historian 2019 (All versions), SIMATIC Process Historian 2020 (All versions). An interface in the software that is used for critical functionalities lacks authentication, which could allow a malicious user to maliciously insert, modify or delete data. | 
    
    
    
        | A vulnerability has been identified in SIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Outdoor Panels V16 7\" & 15\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI Comfort Panels V15 4\" - 22\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Panels V16 4\" - 22\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels V15 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Update 6), SIMATIC HMI KTP Mobile Panels V16 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V16 Update 4), SIMATIC WinCC Runtime Advanced V15 (All versions < V15.1 Update 6), SIMATIC WinCC Runtime Advanced V16 (All versions < V16 Update 4), SINAMICS GH150 (All versions), SINAMICS GL150 (with option X30) (All versions), SINAMICS GM150 (with option X30) (All versions), SINAMICS SH150 (All versions), SINAMICS SL150 (All versions), SINAMICS SM120 (All versions), SINAMICS SM150 (All versions), SINAMICS SM150i (All versions). SmartVNC has a heap allocation leak vulnerability in the device layout handler on client side, which could result in a Denial-of-Service condition. |