CVE-2024-32008 1 Siemens 1 Spectrum Power 4 2026-04-15 7.8 High
A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP12 Update 2). The affected application is vulnerable to a local privilege escalation due to an exposed debug interface on the localhost. This allows any local user to gain code execution as administrative application user.
CVE-2024-41798 1 Siemens 1 Sentron Pac3200 2026-04-15 9.8 Critical
A vulnerability has been identified in SENTRON 7KM PAC3200 (All versions). Affected devices only provide a 4-digit PIN to protect from administrative access via Modbus TCP interface. Attackers with access to the Modbus TCP interface could easily bypass this protection by brute-force attacks or by sniffing the Modbus clear text communication.
CVE-2024-31978 1 Siemens 1 Sinec-nms 2026-04-15 7.6 High
A vulnerability has been identified in SINEC NMS (All versions < V2.0 SP2). Affected devices allow authenticated users to export monitoring data. The corresponding API endpoint is susceptible to path traversal and could allow an authenticated attacker to download files from the file system. Under certain circumstances the downloaded files are deleted from the file system.
CVE-2024-33494 1 Siemens 1 Simatic Rtls Locating Manager 2026-04-15 6.5 Medium
A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected components do not properly authenticate heartbeat messages. This could allow an unauthenticated remote attacker to affected the availability of secondary RTLS systems configured using a TeeRevProxy service and potentially cause loss of data generated during the time the attack is ongoing.
CVE-2025-40753 1 Siemens 2 Q100, Q200 2026-04-15 6.2 Medium
A vulnerability has been identified in POWER METER SICAM Q100 (7KG9501-0AA01-0AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA01-2AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA31-0AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA31-2AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q200 family (All versions >= V2.70 < V2.80). Affected devices export the password for the SMTP account as plain text in the Configuration File. This could allow an authenticated local attacker to extract it and use the configured SMTP service for arbitrary purposes.
CVE-2024-32009 1 Siemens 1 Spectrum Power 4 2026-04-15 7.8 High
A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP12 Update 2). The affected application is vulnerable to a local privilege escalation due to wrongly set permissions to a binary which allows any local attacker to gain administrative privileges.
CVE-2024-30206 1 Siemens 1 Simatic Rtls Locating Manager 2026-04-15 8.8 High
A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected SIMATIC RTLS Locating Manager Clients do not properly check the integrity of update files. This could allow an unauthenticated remote attacker to alter update files in transit and trick an authorized user into installing malicious code. A successful exploit requires the attacker to be able to modify the communication between server and client on the network.
CVE-2024-22041 1 Siemens 13 Cerberus Pro En Engineering Tool, Cerberus Pro En Fire Panel Fc72x, Cerberus Pro En X200 Cloud Distribution and 10 more 2026-04-15 7.5 High
A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems improperly handles memory buffers when parsing X.509 certificates. This could allow an unauthenticated remote attacker to crash the network service.
CVE-2025-40820 1 Siemens 16 Sidoor Atd430w, Sidoor Ate530s Coated, Simatic and 13 more 2026-04-15 7.5 High
Affected products do not properly enforce TCP sequence number validation in specific scenarios but accept values within a broad range. This could allow an unauthenticated remote attacker e.g. to interfere with connection setup, potentially leading to a denial of service. The attack succeeds only if an attacker can inject IP packets with spoofed addresses at precisely timed moments, and it affects only TCP-based services.
CVE-2025-40587 1 Siemens 1 Polarion 2026-04-15 7.6 High
A vulnerability has been identified in Polarion V2404 (All versions < V2404.5), Polarion V2410 (All versions < V2410.2). The affected application allows arbitrary JavaScript code be included in document titles. This could allow an authenticated remote attacker to conduct a stored cross-site scripting attack by creating specially crafted document titles that are later viewed by other users of the application.
CVE-2024-32010 1 Siemens 1 Spectrum Power 4 2026-04-15 7.8 High
A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP12 Update 2). The affected application is vulnerable to extraction of database credentials via a world-readable credential file. This allows an attacker to connect to the database as privileged application user and to run system commands via the database.
CVE-2024-43647 1 Siemens 14 Simatic S7-200 Smart Cpu Cr20s, Simatic S7-200 Smart Cpu Cr30s, Simatic S7-200 Smart Cpu Cr40 and 11 more 2026-04-15 7.5 High
A vulnerability has been identified in SIMATIC S7-200 SMART CPU CR40 (6ES7288-1CR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU CR60 (6ES7288-1CR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA1) (All versions). Affected devices do not properly handle TCP packets with an incorrect structure. This could allow an unauthenticated remote attacker to cause a denial of service condition. To restore normal operations, the network cable of the device needs to be unplugged and re-plugged.
CVE-2023-52238 1 Siemens 2 Ruggedcom Rst2228, Ruggedcom Rst2228p 2026-04-15 4.3 Medium
A vulnerability has been identified in RUGGEDCOM RST2228 (All versions < V5.9.0), RUGGEDCOM RST2228P (All versions < V5.9.0). The web server of the affected systems leaks the MACSEC key in clear text to a logged in user. An attacker with the credentials of a low privileged user could retrieve the MACSEC key and access (decrypt) the ethernet frames sent by authorized recipients.
CVE-2026-27664 1 Siemens 2 Cpci85 Central Processing\/communication, Sicore Base System 2026-04-14 7.5 High
A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V26.10), SICORE Base system (All versions < V26.10.0). The affected application contains an out-of-bounds write vulnerability while parsing specially crafted XML inputs. This could allow an unauthenticated attacker to exploit this issue by sending a malicious XML request, which may cause the service to crash, resulting in a denial-of-service condition.
CVE-2026-27663 1 Siemens 2 Cpci85 Central Processing\/communication, Rtum85 rtu Base 2026-04-14 6.5 Medium
A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V26.10), RTUM85 RTU Base (All versions < V26.10). The affected application contains denial-of-service (DoS) vulnerability. The remote operation mode is susceptible to a resource exhaustion condition when subjected to a high volume of requests. Sending multiple requests can exhaust resources, preventing parameterization and requiring a reset or reboot to restore functionality.
CVE-2020-26147 5 Arista, Debian, Linux and 2 more 15 C-65, C-65 Firmware, C-75 and 12 more 2026-04-14 5.4 Medium
An issue was discovered in the Linux kernel 5.8.9. The WEP, WPA, WPA2, and WPA3 implementations reassemble fragments even though some of them were sent in plaintext. This vulnerability can be abused to inject packets and/or exfiltrate selected fragments when another device sends fragmented frames and the WEP, CCMP, or GCMP data-confidentiality protocol is used.
CVE-2023-44373 1 Siemens 142 6ag1206-2bb00-7ac2, 6ag1206-2bb00-7ac2 Firmware, 6ag1206-2bs00-7ac2 and 139 more 2026-04-14 9.1 Critical
Affected devices do not properly sanitize an input field. This could allow an authenticated remote attacker with administrative privileges to inject code or spawn a system root shell. Follow-up of CVE-2022-36323.
CVE-2022-36325 1 Siemens 180 Scalance M-800, Scalance M-800 Firmware, Scalance S615 and 177 more 2026-04-14 6.8 Medium
Affected devices do not properly sanitize data introduced by an user when rendering the web interface. This could allow an authenticated remote attacker with administrative privileges to inject code and lead to a DOM-based XSS.
CVE-2022-36324 1 Siemens 168 Scalance M-800, Scalance M-800 Firmware, Scalance S615 and 165 more 2026-04-14 7.5 High
Affected devices do not properly handle the renegotiation of SSL/TLS parameters. This could allow an unauthenticated remote attacker to bypass the TCP brute force prevention and lead to a denial of service condition for the duration of the attack.
CVE-2022-36323 1 Siemens 180 Scalance M-800, Scalance M-800 Firmware, Scalance S615 and 177 more 2026-04-14 9.1 Critical
Affected devices do not properly sanitize an input field. This could allow an authenticated remote attacker with administrative privileges to inject code or spawn a system root shell.