CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers. |
A CWE-538: File and Directory Information Exposure vulnerability exists in Modicon M580, Modicon M340, Modicon Premium , Modicon Quantum (all firmware versions), which could cause the disclosure of information from the controller when using TFTP protocol. |
A CWE-200: Information Exposure vulnerability exists in Modicon M580, Modicon BMENOC 0311, and Modicon BMENOC 0321, which could cause the disclosure of sensitive information when reading specific registers with the REST API of the controller/communication module. |
A CWE-200: Information Exposure vulnerability exists in Modicon M580, Modicon BMENOC 0311, and Modicon BMENOC 0321, which could cause the disclosure of sensitive information when using specific Modbus services provided by the REST API of the controller/communication module. |
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580 CPU (BMEx58*) and Modicon M580 communication module (BMENOC0311, BMENOC0321) (see notification for version info), which could cause a Denial of Service attack on the PLC when sending specific data on the REST API of the controller/communication module. |
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service attack on the FTP service when upgrading the firmware with a version incompatible with the application in the controller using FTP protocol. |
A CWE-319: Cleartext Transmission of Sensitive Information vulnerability exists in Modicon M580, Modicon M340, Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause information disclosure when using the FTP protocol. |
A CWE-319: Cleartext Transmission of Sensitive Information vulnerability exists in Modicon M580, Modicon M340, Modicon Premium , Modicon Quantum (all firmware versions), which could cause the disclosure of information when transferring applications to the controller using Modbus TCP protocol. |
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service atack on the PLC when upgrading the controller with a firmware package containing an invalid web server image using FTP protocol. |
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580 with firmware (version prior to V3.10), Modicon M340 (all firmware versions), and Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service attack on the PLC when upgrading the controller with an empty firmware package using FTP protocol. |
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service attack on the PLC when upgrading the firmware with a missing web server image inside the package using FTP protocol. |
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580 with firmware (version prior to V3.10), Modicon M340 (all firmware versions), and Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service attack on the PLC when upgrading the firmware with no firmware image inside the package using FTP protocol. |
A CWE-248: Uncaught Exception vulnerability exists IN Modicon M580 all versions prior to V2.80, which could cause a possible denial of service when sending an appropriately timed HTTP request to the controller. |
A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware version prior to V2.90) and Modicon M340 (firmware version prior to V3.10), which could cause a possible denial of service when writing to specific memory addresses in the controller over Modbus. |
A CWE-248: Uncaught Exception vulnerability exists Modicon M580 (firmware version prior to V2.90), Modicon M340 (firmware version prior to V3.10), Modicon Premium (all versions), and Modicon Quantum (all versions), which could cause a possible denial of service when reading specific coils and registers in the controller over Modbus. |
CWE-330: Use of Insufficiently Random Values vulnerability, which could cause the hijacking of the TCP connection when using Ethernet communication in Modicon M580 firmware versions prior to V2.30, and all firmware versions of Modicon M340, Modicon Premium, Modicon Quantum. |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists which could cause a possible Denial of Service when specific Modbus frames are sent to the controller in the products: Modicon M340 - firmware versions prior to V3.01, Modicon M580 - firmware versions prior to V2.80, All firmware versions of Modicon Quantum and Modicon Premium. |
A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware versions prior to V2.90), Modicon M340 (firmware versions prior to V3.10), Modicon Premium (all versions), Modicon Quantum (all versions), which could cause a possible denial of service when reading invalid data from the controller. |
A CWE-284: Improper Access Control vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a remote code execution by overwriting configuration settings of the controller over Modbus. |
A CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a possible denial of service when writing sensitive application variables to the controller over Modbus. |