Search Results (425 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2018-16561 1 Siemens 8 Simatic S7-300, Simatic S7-300 Firmware, Simatic S7-300f and 5 more 2026-06-02 7.5 High
A vulnerability has been identified in SIMATIC S7-300 CPUs (All versions < V3.X.16). The affected CPUs improperly validate S7 communication packets which could cause a Denial-of-Service condition of the CPU. The CPU will remain in DEFECT mode until manual restart. Successful exploitation requires an attacker to be able to send a specially crafted S7 communication packet to a communication interface of the CPU. This includes Ethernet, PROFIBUS, and Multi Point Interfaces (MPI). No user interaction or privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the core functionality of the CPU, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.
CVE-2016-9158 1 Siemens 21 Simatic S7-300 Cpu 312, Simatic S7-300 Cpu 314, Simatic S7-300 Cpu 315-2 Dp and 18 more 2026-06-02 7.5 High
A vulnerability has been identified in SIMATIC S7-300 CPU family (All versions), SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 V6 and earlier CPU family (All versions), SIMATIC S7-400 V7 CPU family (All versions). Specially crafted packets sent to port 80/tcp could cause the affected devices to go into defect mode. A cold restart is required to recover the system.
CVE-2015-2177 1 Siemens 2 Simatic S7-300 Cpu, Simatic S7-300 Cpu Firmware 2026-06-02 7.5 High
Siemens SIMATIC S7-300 CPU devices allow remote attackers to cause a denial of service (defect-mode transition) via crafted packets on (1) TCP port 102 or (2) Profibus.
CVE-2018-3639 12 Arm, Canonical, Debian and 9 more 330 Cortex-a, Ubuntu Linux, Debian Linux and 327 more 2026-05-29 5.5 Medium
Systems with microprocessors utilizing speculative execution and speculative execution of memory reads before the addresses of all prior memory writes are known may allow unauthorized disclosure of information to an attacker with local user access via a side-channel analysis, aka Speculative Store Bypass (SSB), Variant 4.
CVE-2017-5753 14 Arm, Canonical, Debian and 11 more 396 Cortex-a12, Cortex-a12 Firmware, Cortex-a15 and 393 more 2026-05-28 5.6 Medium
Systems with microprocessors utilizing speculative execution and branch prediction may allow unauthorized disclosure of information to an attacker with local user access via a side-channel analysis.
CVE-2026-22924 1 Siemens 2 Simatic Cn 4100, Simatic Cn 4100 Firmware 2026-05-13 9.1 Critical
A vulnerability has been identified in SIMATIC CN 4100 (All versions < V5.0). The affected application does not properly restrict unauthenticated connections and is susceptible to resource exhaustion conditions. This could allow an attacker to disrupt normal operations or perform unauthorized actions, potentially impacting system availability and integrity.
CVE-2024-50302 5 Debian, Google, Linux and 2 more 42 Debian Linux, Android, Linux Kernel and 39 more 2026-05-12 5.5 Medium
In the Linux kernel, the following vulnerability has been resolved: HID: core: zero-initialize the report buffer Since the report buffer is used by all kinds of drivers in various ways, let's zero-initialize it during allocation to make sure that it can't be ever used to leak kernel memory via specially-crafted report.
CVE-2023-4911 7 Canonical, Debian, Fedoraproject and 4 more 51 Ubuntu Linux, Debian Linux, Fedora and 48 more 2026-05-12 7.8 High
A buffer overflow was discovered in the GNU C Library's dynamic loader ld.so while processing the GLIBC_TUNABLES environment variable. This issue could allow a local attacker to use maliciously crafted GLIBC_TUNABLES environment variables when launching binaries with SUID permission to execute code with elevated privileges.
CVE-2026-22925 1 Siemens 2 Simatic Cn 4100, Simatic Cn 4100 Firmware 2026-05-12 7.5 High
A vulnerability has been identified in SIMATIC CN 4100 (All versions < V5.0). The affected application is susceptible to resource exhaustion when subjected to high volume of TCP SYN packets This could allow an attacker to render the service unavailable and cause denial-of-service conditions by overwhelming system resources.
CVE-2017-5689 3 Hpe, Intel, Siemens 71 Proliant Ml10 Gen9 Server, Proliant Ml10 Gen9 Server Firmware, Active Management Technology Firmware and 68 more 2026-04-22 9.8 Critical
An unprivileged network attacker could gain system privileges to provisioned Intel manageability SKUs: Intel Active Management Technology (AMT) and Intel Standard Manageability (ISM). An unprivileged local attacker could provision manageability features gaining unprivileged network or local system privileges on Intel manageability SKUs: Intel Active Management Technology (AMT), Intel Standard Manageability (ISM), and Intel Small Business Technology (SBT).
CVE-2014-0160 13 Broadcom, Canonical, Debian and 10 more 37 Symantec Messaging Gateway, Ubuntu Linux, Debian Linux and 34 more 2026-04-21 7.5 High
The (1) TLS and (2) DTLS implementations in OpenSSL 1.0.1 before 1.0.1g do not properly handle Heartbeat Extension packets, which allows remote attackers to obtain sensitive information from process memory via crafted packets that trigger a buffer over-read, as demonstrated by reading private keys, related to d1_both.c and t1_lib.c, aka the Heartbleed bug.
CVE-2016-8562 1 Siemens 4 Simatic Cp 1543-1, Simatic Cp 1543-1 Firmware, Siplus Net Cp 1543-1 and 1 more 2026-04-21 7.5 High
A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Under special conditions it was possible to write SNMP variables on port 161/udp which should be read-only and should only be configured with TIA-Portal. A write to these variables could reduce the availability or cause a denial-of-service.
CVE-2024-33495 1 Siemens 1 Simatic Rtls Locating Manager 2026-04-15 6.5 Medium
A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). The affected application does not properly limit the size of specific logs. This could allow an unauthenticated remote attacker to exhaust system resources by creating a great number of log entries which could potentially lead to a denial of service condition. A successful exploitation requires the attacker to have access to specific SIMATIC RTLS Locating Manager Clients in the deployment.
CVE-2011-20002 1 Siemens 3 Simatic, Simatic S7-1200, Simatic S7-1200 Cpu 2026-04-15 7.4 High
A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured.
CVE-2024-30207 1 Siemens 1 Simatic Rtls Locating Manager 2026-04-15 10 Critical
A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). The affected systems use symmetric cryptography with a hard-coded key to protect the communication between client and server. This could allow an unauthenticated remote attacker to compromise confidentiality and integrity of the communication and, subsequently, availability of the system. A successful exploit requires the attacker to gain knowledge of the hard-coded key and to be able to intercept the communication between client and server on the network.
CVE-2024-33496 1 Siemens 1 Simatic Rtls Locating Manager 2026-04-15 6.3 Medium
A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected SIMATIC RTLS Locating Manager Report Clients do not properly protect credentials that are used to authenticate to the server. This could allow an authenticated local attacker to extract the credentials and use them to escalate their access rights from the Manager to the Systemadministrator role.
CVE-2025-23403 1 Siemens 2 Simatic Ipc Diagbase, Simatic Ipc Diagmonitor 2026-04-15 7 High
A vulnerability has been identified in SIMATIC IPC DiagBase (All versions), SIMATIC IPC DiagMonitor (All versions). The affected device do not properly restrict the user permission for the registry key. This could allow an authenticated attacker to load vulnerable drivers into the system leading to privilege escalation or bypassing endpoint protection and other security measures.
CVE-2022-45147 1 Siemens 2 Simatic Pcs Neo, Simatic Step 7 2026-04-15 7.8 High
A vulnerability has been identified in SIMATIC PCS neo V4.0 (All versions), SIMATIC STEP 7 V16 (All versions), SIMATIC STEP 7 V17 (All versions), SIMATIC STEP 7 V18 (All versions < V18 Update 2). Affected applications do not properly restrict the .NET BinaryFormatter when deserializing user-controllable input. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application. This is the same issue that exists for .NET BinaryFormatter https://docs.microsoft.com/en-us/visualstudio/code-quality/ca2300.
CVE-2025-40804 1 Siemens 1 Simatic 2026-04-15 9.1 Critical
A vulnerability has been identified in SIMATIC Virtualization as a Service (SIVaaS) (All versions). The affected application exposes a network share without any authentication. This could allow an attacker to access or alter sensitive data without proper authorization.
CVE-2023-52891 1 Siemens 6 Simatic Energy Manager Basic, Simatic Energy Manager Pro, Simatic Ipc Diagbase and 3 more 2026-04-15 5.3 Medium
A vulnerability has been identified in SIMATIC Energy Manager Basic (All versions < V7.5), SIMATIC Energy Manager PRO (All versions < V7.5), SIMATIC IPC DiagBase (All versions), SIMATIC IPC DiagMonitor (All versions), SIMIT V10 (All versions), SIMIT V11 (All versions < V11.1). Unified Automation .NET based OPC UA Server SDK before 3.2.2 used in Siemens products are affected by a similar vulnerability as documented in CVE-2023-27321 for the OPC Foundation UA .NET Standard implementation. A successful attack may lead to high load situation and memory exhaustion, and may block the server.