Filtered by vendor Schneider-electric Subscriptions
Total 753 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2022-22811 1 Schneider-electric 6 Fellerlynk, Fellerlynk Firmware, Spacelynk and 3 more 2024-08-03 8.1 High
A CWE-352: Cross-Site Request Forgery (CSRF) vulnerability exists that could induce users to perform unintended actions, leading to the override of the system�s configurations when an attacker persuades a user to visit a rogue website. Affected Product: spaceLYnk (V2.6.2 and prior), Wiser for KNX (formerly homeLYnk) (V2.6.2 and prior), fellerLYnk (V2.6.2 and prior)
CVE-2022-22809 1 Schneider-electric 6 Fellerlynk, Fellerlynk Firmware, Spacelynk and 3 more 2024-08-03 5.3 Medium
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could allow modifications of the touch configurations in an unauthorized manner when an attacker attempts to modify the touch configurations. Affected Product: spaceLYnk (V2.6.2 and prior), Wiser for KNX (formerly homeLYnk) (V2.6.2 and prior), fellerLYnk (V2.6.2 and prior)
CVE-2022-22805 1 Schneider-electric 16 Scl Series 1029 Ups, Scl Series 1029 Ups Firmware, Scl Series 1030 Ups and 13 more 2024-08-03 9.8 Critical
A CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') vulnerability exists that could cause remote code execution when an improperly handled TLS packet is reassembled. Affected Product: SmartConnect Family: SMT Series (SMT Series ID=1015: UPS 04.5 and prior), SMC Series (SMC Series ID=1018: UPS 04.2 and prior), SMTL Series (SMTL Series ID=1026: UPS 02.9 and prior), SCL Series (SCL Series ID=1029: UPS 02.5 and prior / SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior / SCL Series ID=1037: UPS 03.1 and prior), SMX Series (SMX Series ID=1031: UPS 03.1 and prior)
CVE-2022-22807 1 Schneider-electric 14 Hmibscea53d1edb, Hmibscea53d1edb Firmware, Hmibscea53d1edl and 11 more 2024-08-03 7.4 High
A CWE-1021 Improper Restriction of Rendered UI Layers or Frames vulnerability exists that could cause unintended modifications of the product settings or user accounts when deceiving the user to use the web interface rendered within iframes. Affected Product: EcoStruxure EV Charging Expert (formerly known as EVlink Load Management System): (HMIBSCEA53D1EDB, HMIBSCEA53D1EDS, HMIBSCEA53D1EDM, HMIBSCEA53D1EDL, HMIBSCEA53D1ESS, HMIBSCEA53D1ESM, HMIBSCEA53D1EML) (All Versions prior to SP8 (Version 01) V4.0.0.13)
CVE-2022-22806 1 Schneider-electric 16 Scl Series 1029 Ups, Scl Series 1029 Ups Firmware, Scl Series 1030 Ups and 13 more 2024-08-03 9.8 Critical
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause an unauthenticated connection to the UPS when a malformed connection is sent. Affected Product: SmartConnect Family: SMT Series (SMT Series ID=1015: UPS 04.5 and prior), SMC Series (SMC Series ID=1018: UPS 04.2 and prior), SMTL Series (SMTL Series ID=1026: UPS 02.9 and prior), SCL Series (SCL Series ID=1029: UPS 02.5 and prior / SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior / SCL Series ID=1037: UPS 03.1 and prior), SMX Series (SMX Series ID=1031: UPS 03.1 and prior)
CVE-2022-22810 1 Schneider-electric 6 Fellerlynk, Fellerlynk Firmware, Spacelynk and 3 more 2024-08-03 9.8 Critical
A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists that could allow an attacker to manipulate the admin after numerous attempts at guessing credentials. Affected Product: spaceLYnk (V2.6.2 and prior), Wiser for KNX (formerly homeLYnk) (V2.6.2 and prior), fellerLYnk (V2.6.2 and prior)
CVE-2022-22813 1 Schneider-electric 66 Easergy P141, Easergy P141 Firmware, Easergy P142 and 63 more 2024-08-03 9.8 Critical
A CWE-798: Use of Hard-coded Credentials vulnerability exists. If an attacker were to obtain the TLS cryptographic key and take active control of the Courier tunneling communication network, they could potentially observe and manipulate traffic associated with product configuration.
CVE-2022-22812 1 Schneider-electric 6 Fellerlynk, Fellerlynk Firmware, Spacelynk and 3 more 2024-08-03 6.1 Medium
A CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause a web session compromise when an attacker injects and then executes arbitrary malicious JavaScript code inside the target browser. Affected Product: spaceLYnk (V2.6.2 and prior), Wiser for KNX (formerly homeLYnk) (V2.6.2 and prior), fellerLYnk (V2.6.2 and prior)
CVE-2022-22808 1 Schneider-electric 14 Hmibscea53d1edb, Hmibscea53d1edb Firmware, Hmibscea53d1edl and 11 more 2024-08-03 8.8 High
A CWE-352: Cross-Site Request Forgery (CSRF) exists that could cause a remote attacker to gain unauthorized access to the product when conducting cross-domain attacks based on same-origin policy or cross-site request forgery protections bypass. Affected Product: EcoStruxure EV Charging Expert (formerly known as EVlink Load Management System): (HMIBSCEA53D1EDB, HMIBSCEA53D1EDS, HMIBSCEA53D1EDM, HMIBSCEA53D1EDL, HMIBSCEA53D1ESS, HMIBSCEA53D1ESM, HMIBSCEA53D1EML) (All Versions prior to SP8 (Version 01) V4.0.0.13)
CVE-2022-22804 1 Schneider-electric 1 Ecostruxure Power Monitoring Expert 2024-08-03 5.4 Medium
A CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could allow an authenticated attacker to view data, change settings, or impact availability of the software when the user visits a page containing the injected payload. Affected Product: EcoStruxure Power Monitoring Expert (Versions 2020 and prior)
CVE-2022-22722 1 Schneider-electric 2 Easergy P5, Easergy P5 Firmware 2024-08-03 7.5 High
A CWE-798: Use of Hard-coded Credentials vulnerability exists that could result in information disclosure. If an attacker were to obtain the SSH cryptographic key for the device and take active control of the local operational network connected to the product they could potentially observe and manipulate traffic associated with product configuration. Affected Product: Easergy P5 (All firmware versions prior to V01.401.101)
CVE-2022-22724 1 Schneider-electric 12 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 9 more 2024-08-03 7.5 High
A CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause a denial of service on ports 80 (HTTP) and 502 (Modbus), when sending a large number of TCP RST or FIN packets to any open TCP port of the PLC. Affected Product: Modicon M340 CPUs: BMXP34 (All Versions)
CVE-2022-22725 1 Schneider-electric 2 Easergy P3, Easergy P3 Firmware 2024-08-03 8.8 High
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could lead to a buffer overflow causing program crashes and arbitrary code execution when specially crafted packets are sent to the device over the network. Protection functions and tripping function via GOOSE can be impacted. Affected Product: Easergy P3 (All versions prior to V30.205)
CVE-2022-22726 1 Schneider-electric 1 Ecostruxure Power Monitoring Expert 2024-08-03 6.5 Medium
A CWE-20: Improper Input Validation vulnerability exists that could allow arbitrary files on the server to be read by authenticated users through a limited operating system service account. Affected Product: EcoStruxure Power Monitoring Expert (Versions 2020 and prior)
CVE-2022-22723 1 Schneider-electric 2 Easergy P5, Easergy P5 Firmware 2024-08-03 8.8 High
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could lead to a buffer overflow causing program crashes and arbitrary code execution when specially crafted packets are sent to the device over the network. Protection functions and tripping function via GOOSE can be impacted. Affected Product: Easergy P5 (All firmware versions prior to V01.401.101)
CVE-2022-22731 1 Schneider-electric 1 Ecostruxure Power Commission 2024-08-03 6.5 Medium
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in a function that could allow an attacker to create or overwrite critical files that are used to execute code, such as programs or libraries and cause path traversal attacks. Affected Products: EcoStruxure Power Commission (Versions prior to V2.22)
CVE-2022-22732 1 Schneider-electric 1 Ecostruxure Power Commission 2024-08-03 3.9 Low
A CWE-668: Exposure of Resource to Wrong Sphere vulnerability exists that could cause all remote domains to access the resources (data) supplied by the server when an attacker sends a fetch request from third-party site or malicious site. Affected Products: EcoStruxure Power Commission (Versions prior to V2.22)
CVE-2022-22727 1 Schneider-electric 1 Ecostruxure Power Monitoring Expert 2024-08-03 8.8 High
A CWE-20: Improper Input Validation vulnerability exists that could allow an unauthenticated attacker to view data, change settings, impact availability of the software, or potentially impact a user�s local machine when the user clicks a specially crafted link. Affected Product: EcoStruxure Power Monitoring Expert (Versions 2020 and prior)
CVE-2022-4062 1 Schneider-electric 1 Ecostruxure Power Commission 2024-08-03 7.8 High
A CWE-285: Improper Authorization vulnerability exists that could cause unauthorized access to certain software functions when an attacker gets access to localhost interface of the EcoStruxure Power Commission application. Affected Products: EcoStruxure Power Commission (Versions prior to V2.25)
CVE-2022-2988 1 Schneider-electric 2 Ecostruxure Machine Expert - Hvac, Somachine Hvac 2024-08-03 4.3 Medium
A CWE-787: Out-of-bounds Write vulnerability exists that could cause sensitive information leakage when accessing a malicious web page from the commissioning software. Affected Products: SoMachine HVAC (Versions prior to V2.1.0), EcoStruxure Machine Expert – HVAC (Versions prior to V1.4.0)