Search Results (83119 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2019-10987 1 Advantech 1 Webaccess 2024-11-21 8.8 High
In WebAccess/SCADA Versions 8.3.5 and prior, multiple out-of-bounds write vulnerabilities are caused by a lack of proper validation of the length of user-supplied data. Exploitation of these vulnerabilities may allow remote code execution.
CVE-2019-10982 1 Deltaww 1 Cnssoft Screeneditor 2024-11-21 7.8 High
Delta Electronics CNCSoft ScreenEditor, Versions 1.00.89 and prior. Multiple heap-based buffer overflow vulnerabilities may be exploited by processing specially crafted project files, allowing an attacker to remotely execute arbitrary code. There is a lack of user input validation before copying data from project files onto the heap.
CVE-2019-10979 1 Sick 2 Msc800, Msc800 Firmware 2024-11-21 N/A
SICK MSC800 all versions prior to Version 4.0, the affected firmware versions contain a hard-coded customer account password.
CVE-2019-10977 1 Mitsubishielectric 2 Qj71e71-100, Qj71e71-100 Firmware 2024-11-21 7.5 High
In Mitsubishi Electric MELSEC-Q series Ethernet module QJ71E71-100 serial number 20121 and prior, an attacker could send crafted TCP packets against the FTP service, forcing the target devices to enter an error mode and cause a denial-of-service condition.
CVE-2019-10974 1 Nrel 1 Energyplus 2024-11-21 5.5 Medium
NREL EnergyPlus, Versions 8.6.0 and possibly prior versions, The application fails to prevent an exception handler from being overwritten with arbitrary code.
CVE-2019-10972 1 Mitsubishielectric 1 Electric Fr Configurator2 2024-11-21 5.5 Medium
Mitsubishi Electric FR Configurator2, Version 1.16S and prior. This vulnerability can be triggered when an attacker provides the target with a rogue project file (.frc2). Once a user opens the rogue project, CPU exhaustion occurs, which causes the software to quit responding until the application is restarted.
CVE-2019-10967 1 Emerson 2 Ovation Ocr400, Ovation Ocr400 Firmware 2024-11-21 8.8 High
In Emerson Ovation OCR400 Controller 3.3.1 and earlier, a stack-based buffer overflow vulnerability in the embedded third-party FTP server involves improper handling of a long file name from the LIST command to the FTP service, which may cause the service to overwrite buffers, leading to remote code execution and escalation of privileges.
CVE-2019-10965 1 Emerson 2 Ovation Ocr400, Ovation Ocr400 Firmware 2024-11-21 8.8 High
In Emerson Ovation OCR400 Controller 3.3.1 and earlier, a heap-based buffer overflow vulnerability in the embedded third-party FTP server involves improper handling of a long command to the FTP service, which may cause memory corruption that halts the controller or leads to remote code execution and escalation of privileges.
CVE-2019-10961 1 Advantech 1 Webaccess Hmi Designer 2024-11-21 8.8 High
In Advantech WebAccess HMI Designer Version 2.1.9.23 and prior, processing specially crafted MCR files lacking proper validation of user supplied data may cause the system to write outside the intended buffer area, allowing remote code execution.
CVE-2019-10958 1 Geutebrueck 22 G-cam Ebc-2110, G-cam Ebc-2110 Firmware, G-cam Ebc-2111 and 19 more 2024-11-21 7.2 High
Geutebruck IP Cameras G-Code(EEC-2xxx), G-Cam(EBC-21xx/EFD-22xx/ETHC-22xx/EWPC-22xx): All versions 1.12.0.25 and prior may allow a remote authenticated attacker with access to network configuration to supply system commands to the server, leading to remote code execution as root.
CVE-2019-10957 1 Geutebrueck 22 G-cam Ebc-2110, G-cam Ebc-2110 Firmware, G-cam Ebc-2111 and 19 more 2024-11-21 4.8 Medium
Geutebruck IP Cameras G-Code(EEC-2xxx), G-Cam(EBC-21xx/EFD-22xx/ETHC-22xx/EWPC-22xx): All versions 1.12.0.25 and prior may allow a remote authenticated attacker with access to event configuration to store malicious code on the server, which could later be triggered by a legitimate user resulting in code execution within the user’s browser.
CVE-2019-10956 1 Geutebrueck 22 G-cam Ebc-2110, G-cam Ebc-2110 Firmware, G-cam Ebc-2111 and 19 more 2024-11-21 7.2 High
Geutebruck IP Cameras G-Code(EEC-2xxx), G-Cam(EBC-21xx/EFD-22xx/ETHC-22xx/EWPC-22xx): All versions 1.12.0.25 and prior may allow a remote authenticated user, using a specially crafted URL command, to execute commands as root.
CVE-2019-10951 1 Deltaww 1 Cncsoft Screeneditor 2024-11-21 7.8 High
Delta Industrial Automation CNCSoft, CNCSoft ScreenEditor Version 1.00.88 and prior. Multiple heap-based buffer overflow vulnerabilities may be exploited by processing specially crafted project files, allowing an attacker to remotely execute arbitrary code. There is a lack of user input validation before copying data from project files onto the heap.
CVE-2019-10947 1 Deltaww 1 Cncsoft Screeneditor 2024-11-21 7.8 High
Delta Industrial Automation CNCSoft, CNCSoft ScreenEditor Version 1.00.88 and prior. Multiple stack-based buffer overflow vulnerabilities may be exploited by processing specially crafted project files, allowing an attacker to remotely execute arbitrary code. This may occur because CNCSoft lacks user input validation before copying data from project files onto the stack.
CVE-2019-10933 1 Siemens 4 Spectrum Power 3, Spectrum Power 4, Spectrum Power 5 and 1 more 2024-11-21 N/A
A vulnerability has been identified in Spectrum Power 3 (Corporate User Interface) (All versions <= v3.11), Spectrum Power 4 (Corporate User Interface) (Version v4.75), Spectrum Power 5 (Corporate User Interface) (All versions < v5.50), Spectrum Power 7 (Corporate User Interface) (All versions <= v2.20). The web server could allow Cross-Site Scripting (XSS) attacks if unsuspecting users are tricked into accessing a malicious link. User interaction is required for a successful exploitation. The user does not need to be logged into the web interface in order for the exploitation to succeed.At the stage of publishing this security advisory no public exploitation is known.
CVE-2019-10928 1 Siemens 2 Scalance Sc-600, Scalance Sc-600 Firmware 2024-11-21 6.6 Medium
A vulnerability has been identified in SCALANCE SC-600 (V2.0). An authenticated attacker with access to port 22/tcp as well as physical access to an affected device may trigger the device to allow execution of arbitrary commands. The security vulnerability could be exploited by an authenticated attacker with physical access to the affected device. No user interaction is required to exploit this vulnerability. The vulnerability impacts the confidentiality, integrity and availability of the affected device.
CVE-2019-10927 1 Siemens 10 Scalance Xb-200, Scalance Xb-200 Firmware, Scalance Xc-200 and 7 more 2024-11-21 6.5 Medium
A vulnerability has been identified in SCALANCE SC-600 (V2.0), SCALANCE XB-200 (V4.1), SCALANCE XC-200 (V4.1), SCALANCE XF-200BA (V4.1), SCALANCE XP-200 (V4.1), SCALANCE XR-300WG (V4.1). An authenticated attacker with network access to to port 22/tcp of an affected device may cause a Denial-of-Service condition. The security vulnerability could be exploited by an authenticated attacker with network access to the affected device. No user interaction is required to exploit this vulnerability. The vulnerability impacts the availability of the affected device.
CVE-2019-10920 1 Siemens 2 Logo\!8 Bm, Logo\!8 Bm Firmware 2024-11-21 7.5 High
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Project data stored on the device, which is accessible via port 10005/tcp, can be decrypted due to a hardcoded encryption key. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 10005/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-10918 1 Siemens 4 Simatic Pcs 7, Simatic Wincc, Simatic Wincc \(tia Portal\) and 1 more 2024-11-21 8.8 High
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An authenticatd attacker with network access to the DCOM interface could execute arbitrary commands with SYSTEM privileges. The vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires authentication with a low-privileged user account and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-10917 1 Siemens 4 Simatic Pcs 7, Simatic Wincc, Simatic Wincc \(tia Portal\) and 1 more 2024-11-21 5.5 Medium
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An attacker with local access to the project file could cause a Denial-of-Service condition on the affected product while the project file is loaded. Successful exploitation requires access to the project file. An attacker could use the vulnerability to compromise availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.