| A vulnerability has been identified in SIMATIC S7-300 CPU family (All versions), SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 V6 and earlier CPU family (All versions), SIMATIC S7-400 V7 CPU family (All versions), SIMATIC S7-410 V8 CPU family (All versions), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions). An attacker with network access to port 102/tcp (ISO-TSAP) or via Profibus could obtain credentials from the PLC if protection-level 2 is configured on the affected devices. |
| Siemens SINEMA Server uses weak permissions for the application folder, which allows local users to gain privileges via unspecified vectors. |
| Siemens SIMATIC STEP 7 (TIA Portal) before 13 SP1 uses a weak password-hash algorithm, which makes it easier for local users to determine cleartext passwords by reading a project file and conducting a brute-force attack. |
| NTP 4.x before 4.2.8p6 and 4.3.x before 4.3.90 do not verify peer associations of symmetric keys when authenticating packets, which might allow remote attackers to conduct impersonation attacks via an arbitrary trusted key, aka a "skeleton key." |
| The web server on Siemens SCALANCE X-200IRT switches with firmware before 5.2.0 allows remote attackers to hijack sessions via unspecified vectors. |
| The Siemens COMPAS Mobile application before 1.6 for Android does not properly verify X.509 certificates from SSL servers, which allows man-in-the-middle attackers to spoof servers and obtain sensitive information via a crafted certificate. |
| The integrated management service on Siemens Ruggedcom WIN51xx devices with firmware before SS4.4.4624.35, WIN52xx devices with firmware before SS4.4.4624.35, WIN70xx devices with firmware before BS4.4.4621.32, and WIN72xx devices with firmware before BS4.4.4621.32 allows remote attackers to bypass authentication and perform administrative actions via unspecified vectors. |
| A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V 4.83; SIPROTEC 7UT686 : All versions < V 4.01; SIPROTEC 7SD686 : All versions < V 4.03; SIPROTEC 7SJ66 : All versions < V 4.20. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive device information if network access was obtained. |
| Cross-site scripting (XSS) vulnerability in the login form in the integrated web server on Siemens OZW OZW672 devices before 6.00 and OZW772 devices before 6.00 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. |
| The following SIEMENS branded IP Camera Models CCMW3025, CVMW3025-IR, CFMW3025 prior to version 1.41_SP18_S1; CCPW3025, CCPW5025 prior to version 0.1.73_S1; CCMD3025-DN18 prior to version v1.394_S1; CCID1445-DN18, CCID1445-DN28, CCID1145-DN36, CFIS1425, CCIS1425, CFMS2025, CCMS2025, CVMS2025-IR, CFMW1025, CCMW1025 prior to version v2635_SP1 could allow an attacker with network access to the web server to obtain administrative credentials under certain circumstances. |
| Cross-site scripting (XSS) vulnerability in the integrated web server in Siemens SINEMA Remote Connect Server before 1.2 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. |
| Siemens SPC controllers SPC4000, SPC5000, and SPC6000 before 3.6.0 allow remote attackers to cause a denial of service (device restart) via crafted packets. |
| The WinCC server in Siemens SIMATIC WinCC 7.0 through SP3, 7.2 before Update 9, and 7.3 before Update 2; SIMATIC PCS 7 7.1 through SP4, 8.0 through SP2, and 8.1; and TIA Portal 13 before Update 6 allows remote attackers to read arbitrary files via crafted packets. |
| Cross-site request forgery (CSRF) vulnerability in the web server on Siemens SIMATIC S7-1200 CPU devices with firmware before 4.1.3 allows remote attackers to hijack the authentication of unspecified victims via unknown vectors. |
| A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server delivers cookies without the "secure" flag. Modern browsers interpreting the flag would mitigate potential data leakage in case of clear text transmission. |
| A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Users with elevated privileges to TIA-Portal and project data on the engineering station could possibly get privileged access on affected devices. |
| A vulnerability in Siemens SICAM PAS (all versions before V8.09) could allow a remote attacker to upload, download, or delete files in certain parts of the file system by sending specially crafted packets to port 19235/TCP. |
| Siemens SIMATIC STEP 7 (TIA Portal) 12 and 13 before 13 SP1 Upd1 allows man-in-the-middle attackers to obtain sensitive information or modify transmitted data via unspecified vectors. |
| The Siemens SIMATIC WinCC Sm@rtClient app before 1.0.2 for iOS allows physically proximate attackers to discover Sm@rtServer credentials by leveraging an error in the credential-processing mechanism. |
| Siemens SICAM PAS before 8.07 does not properly restrict password data in the database, which makes it easier for local users to calculate passwords by leveraging unspecified database privileges. |