| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device. |
| A vulnerability has been identified in SIMATIC WinCC OA V3.15 (All versions < V3.15 P038), SIMATIC WinCC OA V3.16 (All versions < V3.16 P035), SIMATIC WinCC OA V3.17 (All versions < V3.17 P024), SIMATIC WinCC OA V3.18 (All versions < V3.18 P014). The affected component allows to inject custom arguments to the Ultralight Client backend application under certain circumstances.
This could allow an authenticated remote attacker to inject arbitrary parameters when starting the client via the web interface (e.g., open attacker chosen panels with the attacker's credentials or start a Ctrl script). |
| A vulnerability was discovered in Siemens SIMATIC Logon (All versions before V1.6) that could allow specially crafted packets sent to the SIMATIC Logon Remote Access service on port 16389/tcp to cause a Denial-of-Service condition. The service restarts automatically. |
| The MATCH_ASSOC function in NTP before version 4.2.8p9 and 4.3.x before 4.3.92 allows remote attackers to cause an out-of-bounds reference via an addpeer request with a large hmode value. |
| Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually. |
| Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected. |
| Multiple buffer overflows in the ctl_put* functions in NTP before 4.2.8p10 and 4.3.x before 4.3.94 allow remote authenticated users to have unspecified impact via a long variable. |
| A vulnerability was discovered in Siemens SIMATIC WinCC Sm@rtClient for Android (All versions before V1.0.2.2) and SIMATIC WinCC Sm@rtClient for Android Lite (All versions before V1.0.2.2). An attacker with physical access to an unlocked mobile device, that has the affected app running, could bypass the app's authentication mechanism under certain conditions. |
| Siemens SIMATIC Logon prior to V1.5 SP3 Update 2 could allow an attacker with knowledge of a valid user name, and physical or network access to the affected system, to bypass the application-level authentication. |
| A vulnerability has been identified in Primary Setup Tool (PST) (All versions < V4.2 HF1), SIMATIC Automation Tool (All versions < V3.0), SIMATIC NET PC-Software (All versions < V14 SP1), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2), SIMATIC STEP 7 (TIA Portal) V14 (All versions < V14 SP1), SIMATIC STEP 7 V5.X (All versions < V5.6), SIMATIC WinAC RTX 2010 SP2 (All versions), SIMATIC WinAC RTX F 2010 SP2 (All versions), SIMATIC WinCC (TIA Portal) V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1), SIMATIC WinCC V7.2 and prior (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Update 15), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd1), SIMATIC WinCC flexible 2008 (All versions < flexible 2008 SP5), SINAUT ST7CC (All versions installed in conjunction with SIMATIC WinCC < V7.3 Update 15), SINEMA Server (All versions < V14), SINUMERIK 808D Programming Tool (All versions < V4.7 SP4 HF2), SMART PC Access (All versions < V2.3), STEP 7 - Micro/WIN SMART (All versions < V2.3), Security Configuration Tool (SCT) (All versions < V5.0). Specially crafted PROFINET DCP broadcast packets sent to the affected products on a local Ethernet segment (Layer 2) could cause a Denial-of-Service condition of some services. The services require manual restart to recover. |
| A vulnerability was discovered in Siemens SIMATIC WinCC (V7.3 before Upd 11 and V7.4 before SP1), SIMATIC WinCC Runtime Professional (V13 before SP2 and V14 before SP1), SIMATIC WinCC (TIA Portal) Professional (V13 before SP2 and V14 before SP1) that could allow an authenticated, remote attacker who is member of the "administrators" group to crash services by sending specially crafted messages to the DCOM interface. |
| Multiple buffer overflows in Active Management Technology (AMT) in Intel Manageability Engine Firmware 8.x/9.x/10.x/11.0/11.5/11.6/11.7/11.10/11.20 allow attacker with local access to the system to execute arbitrary code with AMT execution privilege. |
| Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. |
| Buffer overflow in Active Management Technology (AMT) in Intel Manageability Engine Firmware 8.x/9.x/10.x/11.0/11.5/11.6/11.7/11.10/11.20 allows attacker with remote Admin access to the system to execute arbitrary code with AMT execution privilege. |
| An XXE vulnerability has been identified in OPC Foundation UA .NET Sample Code before 2017-03-21 and Local Discovery Server (LDS) before 1.03.367. Among the affected products are Siemens SIMATIC PCS7 (All versions V8.1 and earlier), SIMATIC WinCC (All versions < V7.4 SP1), SIMATIC WinCC Runtime Professional (All versions < V14 SP1), SIMATIC NET PC Software, and SIMATIC IT Production Suite. By sending specially crafted packets to the OPC Discovery Server at port 4840/tcp, an attacker might cause the system to access various resources chosen by the attacker. |
| An Improper Input Validation issue was discovered in Siemens SIMATIC PCS 7 V8.1 prior to V8.1 SP1 with WinCC V7.3 Upd 13, and V8.2 all versions. The improper input validation vulnerability has been identified, which may allow an authenticated remote attacker who is a member of the administrators group to crash services by sending specially crafted messages to the DCOM interface. |
| An Improper Authentication issue was discovered in Siemens SIMATIC CP 44x-1 RNA, all versions prior to 1.4.1. An unauthenticated remote attacker may be able to perform administrative actions on the Communication Process (CP) of the RNA series module, if network access to Port 102/TCP is available and the configuration file for the CP is stored on the RNA's CPU. |
| A vulnerability was discovered in Siemens SIMATIC WinCC Sm@rtClient for Android (All versions before V1.0.2.2). The existing TLS protocol implementation could allow an attacker to read and modify data within a TLS session while performing a Man-in-the-Middle (MitM) attack. |
| A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations. |
| A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 Ready4Linux (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packet over port 102/tcp. A restart of the affected device is needed to restore normal operations. |