Siemens APOGEE Insight uses weak permissions for the application folder, which allows local users to obtain sensitive information or modify data via unspecified vectors.
Search vulnerabilities
Siemens SIMATIC STEP 7 (TIA Portal) 12 and 13 before 13 SP1 Upd1 improperly stores password data within project files, which makes it easier for local users to determine cleartext (1) protection-level passwords or (2) web-server passwords by leveraging the ability to read these files.
A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server at port 80/TCP or port 443/TCP of the affected devices could allow remote attackers to perform actions with the permissions of an authenticated user, provided the targeted user has an active session and is induced to trigger the malicious request.
Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted PROFINET packets, a different vulnerability than CVE-2014-2253.
The Siemens HomeControl for Room Automation application before 2.0.1 for Android does not verify X.509 certificates from SSL servers, which allows man-in-the-middle attackers to spoof servers and obtain sensitive information or modify data via a crafted certificate.
The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote attackers to obtain sensitive information via an HTTP request.
The integrated management service on Siemens Ruggedcom WIN51xx devices with firmware before SS4.4.4624.35, WIN52xx devices with firmware before SS4.4.4624.35, WIN70xx devices with firmware before BS4.4.4621.32, and WIN72xx devices with firmware before BS4.4.4621.32 allows remote attackers to bypass authentication and perform administrative actions via unspecified vectors.
Siemens SPC controllers SPC4000, SPC5000, and SPC6000 before 3.6.0 allow remote attackers to cause a denial of service (device restart) via crafted packets.
Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted ISO-TSAP packets, a different vulnerability than CVE-2014-2257.
Open redirect vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors.
Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTP packets.
Siemens SIMATIC WinCC 7.0 through SP3 and 7.2 allows remote attackers to read arbitrary WinCC station files via crafted packets.
Cross-site scripting (XSS) vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTP packets, a different vulnerability than CVE-2014-2255.
The integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject headers via unspecified vectors.
The Siemens SIMATIC WinCC Sm@rtClient app before 1.0.2 for iOS allows physically proximate attackers to discover Sm@rtServer credentials by leveraging an error in the credential-processing mechanism.
Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTPS packets, a different vulnerability than CVE-2014-2259.
The web server on Siemens SCALANCE X-300 switches with firmware before 4.0 and SCALANCE X 408 switches with firmware before 4.0 allows remote attackers to cause a denial of service (reboot) via malformed HTTP requests.
The web management interface in Siemens RuggedCom ROS before 3.11, ROS 3.11 before 3.11.5 for RS950G, ROS 3.12, and ROS 4.0 for RSG2488 allows remote attackers to cause a denial of service (interface outage) via crafted HTTP packets.
A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Users with elevated privileges to TIA-Portal and project data on the engineering station could possibly get privileged access on affected devices.