Filtered by vendor Rockwellautomation
Subscriptions
Total
280 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2020-6984 | 1 Rockwellautomation | 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more | 2024-11-21 | 7.5 High |
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable. | ||||
CVE-2020-6980 | 1 Rockwellautomation | 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more | 2024-11-21 | 3.3 Low |
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, If Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim’s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext. | ||||
CVE-2020-6967 | 1 Rockwellautomation | 1 Factorytalk Services Platform | 2024-11-21 | 9.8 Critical |
In Rockwell Automation all versions of FactoryTalk Diagnostics software, a subsystem of the FactoryTalk Services Platform, FactoryTalk Diagnostics exposes a .NET Remoting endpoint via RNADiagnosticsSrv.exe at TCPtcp/8082, which can insecurely deserialize untrusted data. | ||||
CVE-2020-6111 | 1 Rockwellautomation | 2 Micrologix 1100, Micrologix 1100 B Firmware | 2024-11-21 | 7.5 High |
An exploitable denial-of-service vulnerability exists in the IPv4 functionality of Allen-Bradley MicroLogix 1100 Programmable Logic Controller Systems Series B FRN 16.000, Series B FRN 15.002, Series B FRN 15.000, Series B FRN 14.000, Series B FRN 13.000, Series B FRN 12.000, Series B FRN 11.000 and Series B FRN 10.000. A specially crafted packet can cause a major error, resulting in a denial of service. An attacker can send a malicious packet to trigger this vulnerability. | ||||
CVE-2020-6088 | 1 Rockwellautomation | 2 Flex Io 1794-aent\/b, Flex Io 1794-aent\/b Firmware | 2024-11-21 | 7.5 High |
An exploitable denial of service vulnerability exists in the ENIP Request Path Network Segment functionality of Allen-Bradley Flex IO 1794-AENT/B 4.003. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability. | ||||
CVE-2020-6087 | 1 Rockwellautomation | 2 Flex I\/o 1794-aent\/b, Flex I\/o 1794-aent\/b Firmware | 2024-11-21 | 7.5 High |
An exploitable denial of service vulnerability exists in the ENIP Request Path Data Segment functionality of Allen-Bradley Flex IO 1794-AENT/B. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability If the ANSI Extended Symbol Segment Sub-Type is supplied, the device treats the byte following as the Data Size in words. When this value represents a size greater than what remains in the packet data, the device enters a fault state where communication with the device is lost and a physical power cycle is required. | ||||
CVE-2020-6086 | 1 Rockwellautomation | 2 Flex I\/o 1794-aent\/b, Flex I\/o 1794-aent\/b Firmware | 2024-11-21 | 7.5 High |
An exploitable denial of service vulnerability exists in the ENIP Request Path Data Segment functionality of Allen-Bradley Flex IO 1794-AENT/B. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability.If the Simple Segment Sub-Type is supplied, the device treats the byte following as the Data Size in words. When this value represents a size greater than what remains in the packet data, the device enters a fault state where communication with the device is lost and a physical power cycle is required. | ||||
CVE-2020-6085 | 1 Rockwellautomation | 1 Flex I\/o 1794-aent | 2024-11-21 | 7.5 High |
An exploitable denial of service vulnerability exists in the ENIP Request Path Logical Segment functionality of Allen-Bradley Flex IO 1794-AENT/B 4.003. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability by sending an Electronic Key Segment with less than 0x18 bytes following the Key Format field. | ||||
CVE-2020-6084 | 1 Rockwellautomation | 1 Flex I\/o 1794-aent | 2024-11-21 | 7.5 High |
An exploitable denial of service vulnerability exists in the ENIP Request Path Logical Segment functionality of Allen-Bradley Flex IO 1794-AENT/B 4.003. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability by sending an Electronic Key Segment with less bytes than required by the Key Format Table. | ||||
CVE-2020-6083 | 1 Rockwellautomation | 2 Allen-bradley Flex Io 1794-aent\/b, Allen-bradley Flex Io 1794-aent\/b Firmware | 2024-11-21 | 7.5 High |
An exploitable denial of service vulnerability exists in the ENIP Request Path Port Segment functionality of Allen-Bradley Flex IO 1794-AENT/B. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service. An attacker can send a malicious packet to trigger this vulnerability. | ||||
CVE-2020-5807 | 1 Rockwellautomation | 1 Factorytalk Diagnostics | 2024-11-21 | 7.5 High |
An unauthenticated remote attacker can send data to RsvcHost.exe listening on TCP port 5241 to add entries in the FactoryTalk Diagnostics event log. The attacker can specify long fields in the log entry, which can cause an unhandled exception in wcscpy_s() if a local user opens FactoryTalk Diagnostics Viewer (FTDiagViewer.exe) to view the log entry. Observed in FactoryTalk Diagnostics 6.11. All versions of FactoryTalk Diagnostics are affected. | ||||
CVE-2020-5806 | 1 Rockwellautomation | 1 Factorytalk Linx | 2024-11-21 | 5.5 Medium |
An attacker-controlled memory allocation size can be passed to the C++ new operator in the CServerManager::HandleBrowseLoadIconStreamRequest in messaging.dll. This can be done by sending a specially crafted message to 127.0.0.1:7153. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected. | ||||
CVE-2020-5802 | 1 Rockwellautomation | 1 Factorytalk Linx | 2024-11-21 | 7.5 High |
An attacker-controlled memory allocation size can be passed to the C++ new operator in RnaDaSvr.dll by sending a specially crafted ConfigureItems message to TCP port 4241. This will cause an unhandled exception, resulting in termination of RSLinxNG.exe. Observed in FactoryTalk 6.11. All versions of FactoryTalk Linx are affected. | ||||
CVE-2020-5801 | 1 Rockwellautomation | 1 Factorytalk Linx | 2024-11-21 | 7.5 High |
An attacker can craft and send an OpenNamespace message to port 4241 with valid session-id that triggers an unhandled exception in CFTLDManager::HandleRequest function in RnaDaSvr.dll, resulting in process termination. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected. | ||||
CVE-2020-27267 | 4 Ge, Ptc, Rockwellautomation and 1 more | 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more | 2024-11-21 | 9.1 Critical |
KEPServerEX v6.0 to v6.9, ThingWorx Kepware Server v6.8 and v6.9, ThingWorx Industrial Connectivity (all versions), OPC-Aggregator (all versions), Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server v7.68.804 and v7.66, and Software Toolbox TOP Server all 6.x versions, are vulnerable to a heap-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and potentially leak data. | ||||
CVE-2020-27265 | 4 Ge, Ptc, Rockwellautomation and 1 more | 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more | 2024-11-21 | 9.8 Critical |
KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions are vulnerable to a stack-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and remotely execute code. | ||||
CVE-2020-27263 | 4 Ge, Ptc, Rockwellautomation and 1 more | 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more | 2024-11-21 | 9.1 Critical |
KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions, are vulnerable to a heap-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and potentially leak data. | ||||
CVE-2020-27255 | 1 Rockwellautomation | 1 Factorytalk Linx | 2024-11-21 | 7.5 High |
A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious set attribute requests, which could result in the leaking of sensitive information. This information disclosure could lead to the bypass of address space layout randomization (ASLR). | ||||
CVE-2020-27253 | 1 Rockwellautomation | 1 Factorytalk Linx | 2024-11-21 | 7.5 High |
A flaw exists in the Ingress/Egress checks routine of FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to specifically craft a malicious packet resulting in a denial-of-service condition on the device. | ||||
CVE-2020-27251 | 1 Rockwellautomation | 1 Factorytalk Linx | 2024-11-21 | 9.8 Critical |
A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious port ranges, which could result in remote code execution. |