Filtered by vendor Siemens Subscriptions
Total 1927 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2019-8258 2 Siemens, Uvnc 4 Sinumerik Access Mymachine\/p2p, Sinumerik Pcu Base Win10 Software\/ipc, Sinumerik Pcu Base Win7 Software\/ipc and 1 more 2024-11-21 9.8 Critical
UltraVNC revision 1198 has a heap buffer overflow vulnerability in VNC client code which results code execution. This attack appears to be exploitable via network connectivity. This vulnerability has been fixed in revision 1199.
CVE-2019-6585 1 Siemens 8 Scalance S602, Scalance S602 Firmware, Scalance S612 and 5 more 2024-11-21 6.1 Medium
A vulnerability has been identified in SCALANCE S602 (All versions >= V3.0 and < V4.1), SCALANCE S612 (All versions >= V3.0 and < V4.1), SCALANCE S623 (All versions >= V3.0 and < V4.1), SCALANCE S627-2M (All versions >= V3.0 and < V4.1). The integrated configuration web server of the affected devices could allow Cross-Site Scripting (XSS) attacks if unsuspecting users are tricked into accessing a malicious link. User interaction is required for a successful exploitation. The user must be logged into the web interface in order for the exploitation to succeed.
CVE-2019-6584 1 Siemens 2 Logo\!8, Logo\!8 Firmware 2024-11-21 8.8 High
A vulnerability has been identified in SIEMENS LOGO!8 (6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware version V1.80.xx and V1.81.xx), SIEMENS LOGO!8 (6ED1052-xyy08-0BA0 FS:01 / Firmware version < V1.82.02). The integrated webserver does not invalidate the Session ID upon user logout. An attacker that successfully extracted a valid Session ID is able to use it even after the user logs out. The security vulnerability could be exploited by an attacker in a privileged network position who is able to read the communication between the affected device and the user or by an attacker who is able to obtain valid Session IDs through other means. The user must invoke a session to the affected device. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-6582 1 Siemens 5 Siveillance Video Management Software 2017 R2, Siveillance Video Management Software 2018 R1, Siveillance Video Management Software 2018 R2 and 2 more 2024-11-21 7.1 High
A vulnerability has been identified in Siveillance VMS 2017 R2 (All versions < V11.2a), Siveillance VMS 2018 R1 (All versions < V12.1a), Siveillance VMS 2018 R2 (All versions < V12.2a), Siveillance VMS 2018 R3 (All versions < V12.3a), Siveillance VMS 2019 R1 (All versions < V13.1a). An attacker with network access to port 80/TCP can change user-defined event properties without proper authorization. The security vulnerability could be exploited by an authenticated attacker with network access to the affected service. No user interaction is required to exploit this security vulnerability. Successful exploitation compromises integrity of the user-defined event properties and the availability of corresponding functionality. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-6581 1 Siemens 5 Siveillance Video Management Software 2017 R2, Siveillance Video Management Software 2018 R1, Siveillance Video Management Software 2018 R2 and 2 more 2024-11-21 8.8 High
A vulnerability has been identified in Siveillance VMS 2017 R2 (All versions < V11.2a), Siveillance VMS 2018 R1 (All versions < V12.1a), Siveillance VMS 2018 R2 (All versions < V12.2a), Siveillance VMS 2018 R3 (All versions < V12.3a), Siveillance VMS 2019 R1 (All versions < V13.1a). An attacker with network access to port 80/TCP could change user roles without proper authorization. The security vulnerability could be exploited by an authenticated attacker with network access to the affected service. No user interaction is required to exploit this security vulnerability. Successful exploitation compromises confidentiality, integrity and availability of the targeted system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-6580 1 Siemens 5 Siveillance Video Management Software 2017 R2, Siveillance Video Management Software 2018 R1, Siveillance Video Management Software 2018 R2 and 2 more 2024-11-21 9.8 Critical
A vulnerability has been identified in Siveillance VMS 2017 R2 (All versions < V11.2a), Siveillance VMS 2018 R1 (All versions < V12.1a), Siveillance VMS 2018 R2 (All versions < V12.2a), Siveillance VMS 2018 R3 (All versions < V12.3a), Siveillance VMS 2019 R1 (All versions < V13.1a). An attacker with network access to port 80/TCP could change device properties without authorization. No user interaction is required to exploit this security vulnerability. Successful exploitation compromises confidentiality, integrity and availability of the targeted system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-6579 1 Siemens 1 Spectrum Power 4 2024-11-21 9.8 Critical
A vulnerability has been identified in Spectrum Power 4 (with Web Office Portal). An attacker with network access to the web server on port 80/TCP or 443/TCP could execute system commands with administrative privileges. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected service. No user interaction is required to exploit this security vulnerability. Successful exploitation of the security vulnerability compromises confidentiality, integrity or availability of the targeted system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-6578 1 Siemens 12 Sinamics Perfect Harmony Gh180 With Nxg I Control Mlfb 6sr2, Sinamics Perfect Harmony Gh180 With Nxg I Control Mlfb 6sr2 Firmware, Sinamics Perfect Harmony Gh180 With Nxg I Control Mlfb 6sr3 and 9 more 2024-11-21 7.5 High
A vulnerability has been identified in SINAMICS PERFECT HARMONY GH180 with NXG I control, MLFBs: 6SR2...-, 6SR3...-, 6SR4...- (All Versions with option G28), SINAMICS PERFECT HARMONY GH180 with NXG II control, MLFBs: 6SR2...-, 6SR3...-, 6SR4...- (All Versions with option G28). A denial of service vulnerability exists in the affected products. The vulnerability could be exploited by an attacker with network access to the device. Successful exploitation requires no privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-6577 1 Siemens 22 Simatic Hmi Comfort Outdoor Panels, Simatic Hmi Comfort Outdoor Panels Firmware, Simatic Hmi Comfort Panels and 19 more 2024-11-21 N/A
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The integrated web server could allow Cross-Site Scripting (XSS) attacks if an attacker is able to modify particular parts of the device configuration via SNMP. The security vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires system privileges and user interaction. An attacker could use the vulnerability to compromise confidentiality and the integrity of the affected system. At the stage of publishing this security advisory no public exploitation is known.
CVE-2019-6576 1 Siemens 22 Simatic Hmi Comfort Outdoor Panels, Simatic Hmi Comfort Outdoor Panels Firmware, Simatic Hmi Comfort Panels and 19 more 2024-11-21 N/A
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). An attacker with network access to affected devices could potentially obtain a TLS session key. If the attacker is able to observe TLS traffic between a legitimate user and the device, then the attacker could decrypt the TLS traffic. The security vulnerability could be exploited by an attacker who has network access to the web interface of the device and who is able to observe TLS traffic between legitimate users and the web interface of the affected device. The vulnerability could impact the confidentiality of the communication between the affected device and a legitimate user. At the time of advisory publication no public exploitation of the security vulnerability was known.
CVE-2019-6575 1 Siemens 43 Opc Unified Architecture, Simatic Cp443-1 Opc Ua, Simatic Cp443-1 Opc Ua Firmware and 40 more 2024-11-21 7.5 High
A vulnerability has been identified in SIMATIC CP 443-1 OPC UA (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V2.7), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Upd 4), SIMATIC IPC DiagMonitor (All versions < V5.1.3), SIMATIC NET PC Software V13 (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC RF188C (All versions < V1.1.0), SIMATIC RF600R family (All versions < V3.2.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.5 < V2.6.1), SIMATIC S7-1500 Software Controller (All versions between V2.5 (including) and V2.7 (excluding)), SIMATIC WinCC OA (All versions < V3.15 P018), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Upd 4), SINEC NMS (All versions < V1.0 SP1), SINEMA Server (All versions < V14 SP2), SINUMERIK OPC UA Server (All versions < V2.1), TeleControl Server Basic (All versions < V3.1.1). Specially crafted network packets sent to affected devices on port 4840/tcp could allow an unauthenticated remote attacker to cause a denial of service condition of the OPC communication or crash the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the OPC communication.
CVE-2019-6574 1 Siemens 12 Sinamics Perfect Harmony Gh180 With Nxg I Control Mlfb 6sr2, Sinamics Perfect Harmony Gh180 With Nxg I Control Mlfb 6sr2 Firmware, Sinamics Perfect Harmony Gh180 With Nxg I Control Mlfb 6sr3 and 9 more 2024-11-21 7.5 High
A vulnerability has been identified in SINAMICS PERFECT HARMONY GH180 with NXG I control, MLFBs: 6SR2...-, 6SR3...-, 6SR4...- (All Versions with option G21, G22, G23, G26, G28, G31, G32, G38, G43 or G46), SINAMICS PERFECT HARMONY GH180 with NXG II control, MLFBs: 6SR2...-, 6SR3...-, 6SR4...- (All Versions with option G21, G22, G23, G26, G28, G31, G32, G38, G43 or G46). An improperly configured Parameter Read/Write execution via Field bus network may cause the controller to restart. The vulnerability could be exploited by an attacker with network access to the device. Successful exploitation requires no privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-6572 1 Siemens 22 Simatic Hmi Comfort Outdoor Panels, Simatic Hmi Comfort Outdoor Panels Firmware, Simatic Hmi Comfort Panels and 19 more 2024-11-21 9.1 Critical
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The affected device offered SNMP read and write capacities with a publicly know hardcoded community string. The security vulnerability could be exploited by an attacker with network access to the affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-6571 1 Siemens 2 Logo\!8, Logo\!8 Firmware 2024-11-21 7.5 High
A vulnerability has been identified in SIEMENS LOGO!8 (6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware version V1.80.xx and V1.81.xx), SIEMENS LOGO!8 (6ED1052-xyy08-0BA0 FS:01 / Firmware version < V1.82.02). An attacker with network access to port 10005/tcp of the LOGO! device could cause a Denial-of-Service condition by sending specially crafted packets. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected service. No user interaction is required to exploit this security vulnerability. Successful exploitation of the security vulnerability compromises availability of the targeted system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-6570 1 Siemens 1 Sinema Remote Connect Server 2024-11-21 8.8 High
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V2.0). Due to insufficient checking of user permissions, an attacker may access URLs that require special authorization. An attacker must have access to a low privileged account in order to exploit the vulnerability.
CVE-2019-6569 1 Siemens 10 Scalance X-200, Scalance X-200 Firmware, Scalance X-300 and 7 more 2024-11-21 9.1 Critical
The monitor barrier of the affected products insufficiently blocks data from being forwarded over the mirror port into the mirrored network. An attacker could use this behavior to transmit malicious packets to systems in the mirrored network, possibly influencing their configuration and runtime behavior.
CVE-2019-6568 1 Siemens 100 Cp1604, Cp1604 Firmware, Cp1616 and 97 more 2024-11-21 7.5 High
The webserver of the affected devices contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation which leads to a restart of the webserver of the affected device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the device.
CVE-2019-6567 1 Siemens 8 Scalance X-200, Scalance X-200 Firmware, Scalance X-200irt and 5 more 2024-11-21 5.5 Medium
A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (All Versions < V5.2.4), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.5.0), SCALANCE X-300 switch family (incl. X408 and SIPLUS NET variants) (All versions < V4.1.3), SCALANCE X-414-3E (All versions). The affected devices store passwords in a recoverable format. An attacker may extract and recover device passwords from the device configuration. Successful exploitation requires access to a device configuration backup and impacts confidentiality of the stored passwords.
CVE-2019-6111 10 Apache, Canonical, Debian and 7 more 27 Mina Sshd, Ubuntu Linux, Debian Linux and 24 more 2024-11-21 5.9 Medium
An issue was discovered in OpenSSH 7.9. Due to the scp implementation being derived from 1983 rcp, the server chooses which files/directories are sent to the client. However, the scp client only performs cursory validation of the object name returned (only directory traversal attacks are prevented). A malicious scp server (or Man-in-The-Middle attacker) can overwrite arbitrary files in the scp client target directory. If recursive operation (-r) is performed, the server can manipulate subdirectories as well (for example, to overwrite the .ssh/authorized_keys file).
CVE-2019-6110 4 Netapp, Openbsd, Siemens and 1 more 9 Element Software, Ontap Select Deploy, Storage Automation Store and 6 more 2024-11-21 6.8 Medium
In OpenSSH 7.9, due to accepting and displaying arbitrary stderr output from the server, a malicious server (or Man-in-The-Middle attacker) can manipulate the client output, for example to use ANSI control codes to hide additional files being transferred.