| Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTPS packets, a different vulnerability than CVE-2014-2259. |
| The Siemens SIMATIC WinCC Sm@rtClient app before 1.0.2 for iOS allows local users to bypass an intended application-password requirement by leveraging the running of the app in the background state. |
| Siemens SIMATIC STEP 7 (TIA Portal) before 13 SP1 determines a user's privileges on the basis of project-file fields that lack integrity protection, which allows remote attackers to establish arbitrary authorization data via a modified file. |
| The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a (1) HTTP or (2) HTTPS request. |
| Open redirect vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors. |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTPS packets. |
| A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server delivers cookies without the "secure" flag. Modern browsers interpreting the flag would mitigate potential data leakage in case of clear text transmission. |
| A vulnerability has been identified in SIMATIC S7-300 CPU family (All versions), SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 V6 and earlier CPU family (All versions), SIMATIC S7-400 V7 CPU family (All versions). Specially crafted packets sent to port 80/tcp could cause the affected devices to go into defect mode. A cold restart is required to recover the system. |
| A vulnerability has been identified in SIMATIC S7-300 CPU family (All versions), SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 V6 and earlier CPU family (All versions), SIMATIC S7-400 V7 CPU family (All versions), SIMATIC S7-410 V8 CPU family (All versions), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions). An attacker with network access to port 102/tcp (ISO-TSAP) or via Profibus could obtain credentials from the PLC if protection-level 2 is configured on the affected devices. |
| The random-number generator on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 does not have sufficient entropy, which makes it easier for remote attackers to defeat cryptographic protection mechanisms and hijack sessions via unspecified vectors. |
| A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server at port 80/TCP or port 443/TCP of the affected devices could allow remote attackers to perform actions with the permissions of an authenticated user, provided the targeted user has an active session and is induced to trigger the malicious request. |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTP packets. |
| A vulnerability has been identified in Primary Setup Tool (PST) (All versions < V4.2 HF1), SIMATIC IT Production Suite (All versions < V7.0 SP1 HFX 2), SIMATIC NET PC-Software (All versions < V14), SIMATIC PCS 7 V7.1 (All versions), SIMATIC PCS 7 V8.0 (All versions), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2), SIMATIC STEP 7 V5.X (All versions < V5.5 SP4 HF11), SIMATIC WinCC (TIA Portal) Basic, Comfort, Advanced (All versions < V14), SIMATIC WinCC (TIA Portal) Professional V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) Professional V14 (All versions < V14 SP1), SIMATIC WinCC Runtime Professional V13 (All versions < V13 SP2), SIMATIC WinCC Runtime Professional V14 (All versions < V14 SP1), SIMATIC WinCC V7.0 SP2 and earlier versions (All versions < V7.0 SP2 Upd 12), SIMATIC WinCC V7.0 SP3 (All versions < V7.0 SP3 Upd 8), SIMATIC WinCC V7.2 (All versions < V7.2 Upd 14), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 11), SIMATIC WinCC V7.4 (All versions < V7.4 SP1), SIMIT V9.0 (All versions < V9.0 SP1), SINEMA Remote Connect Client (All versions < V1.0 SP3), SINEMA Server (All versions < V13 SP2), SOFTNET Security Client V5.0 (All versions), Security Configuration Tool (SCT) (All versions < V4.3 HF1), TeleControl Server Basic (All versions < V3.0 SP2), WinAC RTX 2010 SP2 (All versions), WinAC RTX F 2010 SP2 (All versions). Unquoted service paths could allow local Microsoft Windows operating system users to escalate their privileges if the affected products are not installed under their default path ("C:\Program Files\*" or the localized equivalent). |
| Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTP packets, a different vulnerability than CVE-2014-2255. |
| Cross-site scripting (XSS) vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. |
| Siemens SIMATIC HMI Basic Panels 2nd Generation before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC HMI Comfort Panels before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC WinCC Runtime Advanced before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC WinCC Runtime Professional before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC HMI Basic Panels 1st Generation (WinCC TIA Portal), SIMATIC HMI Mobile Panel 277 (WinCC TIA Portal), SIMATIC HMI Multi Panels (WinCC TIA Portal), and SIMATIC WinCC 7.x before 7.3 Upd4 allow remote attackers to complete authentication by leveraging knowledge of a password hash without knowledge of the associated password. |
| Siemens SIMATIC S7-300 Profinet-enabled CPU devices with firmware before 3.2.12 and SIMATIC S7-300 Profinet-disabled CPU devices with firmware before 3.3.12 allow remote attackers to cause a denial of service (defect-mode transition) via crafted (1) ISO-TSAP or (2) Profibus packets. |
| Open redirect vulnerability in the integrated web server on Siemens SIMATIC S7-1200 CPU devices with firmware before 4.1 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors. |
| A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Users with elevated privileges to TIA-Portal and project data on the engineering station could possibly get privileged access on affected devices. |
| Siemens SIMATIC S7-1500 CPU devices before 1.8.3 allow remote attackers to bypass a replay protection mechanism via packets on TCP port 102. |