Filtered by vendor Rockwellautomation Subscriptions
Total 280 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2020-12005 1 Rockwellautomation 2 Factorytalk Linx, Rslinx Classic 2024-11-21 7.5 High
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. A vulnerability exists in the communication function that enables users to upload EDS files by FactoryTalk Linx. This may allow an attacker to upload a file with bad compression, consuming all the available CPU resources, leading to a denial-of-service condition.
CVE-2020-12003 1 Rockwellautomation 2 Factorytalk Linx, Rslinx Classic 2024-11-21 7.5 High
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. An exposed API call allows users to provide files to be processed without sanitation. This may allow an attacker to use specially crafted requests to traverse the file system and expose sensitive data on the local hard drive.
CVE-2020-12001 1 Rockwellautomation 2 Factorytalk Linx, Rslinx Classic 2024-11-21 9.8 Critical
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. The parsing mechanism that processes certain file types does not provide input sanitation. This may allow an attacker to use specially crafted files to traverse the file system and modify or expose sensitive data or execute arbitrary code.
CVE-2020-11999 1 Rockwellautomation 2 Factorytalk Linx, Rslinx Classic 2024-11-21 8.1 High
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. An exposed API call allows users to provide files to be processed without sanitation. This may allow an attacker to specify a filename to execute unauthorized code and modify files or data.
CVE-2020-10642 1 Rockwellautomation 1 Rslinx Classic 2024-11-21 7.8 High
In Rockwell Automation RSLinx Classic versions 4.11.00 and prior, an authenticated local attacker could modify a registry key, which could lead to the execution of malicious code using system privileges when opening RSLinx Classic.
CVE-2019-6553 1 Rockwellautomation 1 Rslinx 2024-11-21 9.8 Critical
A vulnerability was found in Rockwell Automation RSLinx Classic versions 4.10.00 and prior. An input validation issue in a .dll file of RSLinx Classic where the data in a Forward Open service request is passed to a fixed size buffer, allowing an attacker to exploit a stack-based buffer overflow condition.
CVE-2019-13527 1 Rockwellautomation 1 Arena Simulation Software 2024-11-21 7.8 High
In Rockwell Automation Arena Simulation Software Cat. 9502-Ax, Versions 16.00.00 and earlier, a maliciously crafted Arena file opened by an unsuspecting user may result in the use of a pointer that has not been initialized.
CVE-2019-13521 1 Rockwellautomation 1 Arena Simulation 2024-11-21 7.8 High
A maliciously crafted program file opened by an unsuspecting user of Rockwell Automation Arena Simulation Software version 16.00.00 and earlier may result in the limited exposure of information related to the targeted workstation. Rockwell Automation has released version 16.00.01 of Arena Simulation Software to address the reported vulnerabilities.
CVE-2019-13519 1 Rockwellautomation 1 Arena Simulation 2024-11-21 7.8 High
A maliciously crafted program file opened by an unsuspecting user of Rockwell Automation Arena Simulation Software version 16.00.00 and earlier may result in the limited exposure of information related to the targeted workstation. Rockwell Automation has released version 16.00.01 of Arena Simulation Software to address the reported vulnerabilities.
CVE-2019-13511 1 Rockwellautomation 1 Arena Simulation Software 2024-11-21 3.3 Low
Rockwell Automation Arena Simulation Software versions 16.00.00 and earlier contain an INFORMATION EXPOSURE CWE-200. A maliciously crafted Arena file opened by an unsuspecting user may result in the limited exposure of information related to the targeted workstation.
CVE-2019-13510 1 Rockwellautomation 1 Arena Simulation Software 2024-11-21 N/A
Rockwell Automation Arena Simulation Software versions 16.00.00 and earlier contain a USE AFTER FREE CWE-416. A maliciously crafted Arena file opened by an unsuspecting user may result in the application crashing or the execution of arbitrary code.
CVE-2019-10970 1 Rockwellautomation 2 Panelview 5510, Panelview 5510 Firmware 2024-11-21 9.8 Critical
In Rockwell Automation PanelView 5510 (all versions manufactured before March 13, 2019 that have never been updated to v4.003, v5.002, or later), a remote, unauthenticated threat actor with access to an affected PanelView 5510 Graphic Display, upon successful exploit, may boot-up the terminal and gain root-level access to the device’s file system.
CVE-2019-10955 1 Rockwellautomation 11 Compactlogix 5370 L1, Compactlogix 5370 L1 Firmware, Compactlogix 5370 L2 and 8 more 2024-11-21 N/A
In Rockwell Automation MicroLogix 1400 Controllers Series A, All Versions Series B, v15.002 and earlier, MicroLogix 1100 Controllers v14.00 and earlier, CompactLogix 5370 L1 controllers v30.014 and earlier, CompactLogix 5370 L2 controllers v30.014 and earlier, CompactLogix 5370 L3 controllers (includes CompactLogix GuardLogix controllers) v30.014 and earlier, an open redirect vulnerability could allow a remote unauthenticated attacker to input a malicious link to redirect users to a malicious site that could run or download arbitrary malware on the user’s machine.
CVE-2019-10954 1 Rockwellautomation 10 Armor Compact Guardlogix 5370, Armor Compact Guardlogix 5370 Firmware, Compact Guardlogix 5370 and 7 more 2024-11-21 7.5 High
An attacker could send crafted SMTP packets to cause a denial-of-service condition where the controller enters a major non-recoverable faulted state (MNRF) in CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier.
CVE-2019-10952 1 Rockwellautomation 8 Armor Compact Guardlogix 5370, Armor Compact Guardlogix 5370 Firmware, Compactlogix 5370 L1 and 5 more 2024-11-21 9.8 Critical
An attacker could send a crafted HTTP/HTTPS request to render the web server unavailable and/or lead to remote code execution caused by a stack-based buffer overflow vulnerability. A cold restart is required for recovering CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier.
CVE-2018-8843 1 Rockwellautomation 1 Arena 2024-11-21 N/A
Rockwell Automation Arena versions 15.10.00 and prior contains a use after free vulnerability caused by processing specially crafted Arena Simulation Software files that may cause the software application to crash, potentially losing any unsaved data..
CVE-2018-19616 1 Rockwellautomation 2 Powermonitor 1000, Powermonitor 1000 Firmware 2024-11-21 N/A
An issue was discovered in Rockwell Automation Allen-Bradley PowerMonitor 1000. An unauthenticated user can add/edit/remove administrators because access control is implemented on the client side via a disabled attribute for a BUTTON element.
CVE-2018-19615 1 Rockwellautomation 2 Powermonitor 1000, Powermonitor 1000 Firmware 2024-11-21 6.1 Medium
Rockwell Automation Allen-Bradley PowerMonitor 1000 all versions. A remote attacker could inject arbitrary code into a targeted user’s web browser to gain access to the affected device.
CVE-2018-19282 1 Rockwellautomation 2 Powerflex 525 Ac Drives, Powerflex 525 Ac Drives Firmware 2024-11-21 N/A
Rockwell Automation PowerFlex 525 AC Drives 5.001 and earlier allow remote attackers to cause a denial of service by crashing the Common Industrial Protocol (CIP) network stack. The vulnerability allows the attacker to crash the CIP in a way that it does not accept new connections, but keeps the current connections active, which can prevent legitimate users from recovering control.
CVE-2018-19016 1 Rockwellautomation 2 Ethernet\/ip Web Server Module 1756-eweb, Ethernet\/ip Web Server Module 1768-eweb 2024-11-21 N/A
Rockwell Automation EtherNet/IP Web Server Modules 1756-EWEB (includes 1756-EWEBK) Version 5.001 and earlier, and CompactLogix 1768-EWEB Version 2.005 and earlier. A remote attacker could send a crafted UDP packet to the SNMP service causing a denial-of-service condition to occur until the affected product is restarted.