Filtered by vendor Rockwellautomation Subscriptions
Filtered by product Compactlogix 5380 Firmware Subscriptions
Total 7 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2024-6077 1 Rockwellautomation 18 1756-en4, 1756-en4 Firmware, Compact Guardlogix 5380 Sil2 Firmware and 15 more 2024-09-19 7.5 High
A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover.
CVE-2022-1161 1 Rockwellautomation 48 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 45 more 2024-09-16 10 Critical
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.
CVE-2024-7515 1 Rockwellautomation 5 Compact Guardlogix 5380 Firmware, Compactlogix 5380 Firmware, Compactlogix 5480 Firmware and 2 more 2024-08-15 N/A
CVE-2024-7515 IMPACT A denial-of-service vulnerability exists in the affected products. A malformed PTP management packet can cause a major nonrecoverable fault in the controller.
CVE-2017-6024 1 Rockwellautomation 4 Compactlogix 5380, Compactlogix 5380 Firmware, Controllogix 5580 and 1 more 2024-08-05 5.9 Medium
A Resource Exhaustion issue was discovered in Rockwell Automation ControlLogix 5580 controllers V28.011, V28.012, and V28.013; ControlLogix 5580 controllers V29.011; CompactLogix 5380 controllers V28.011; and CompactLogix 5380 controllers V29.011. This vulnerability may allow an attacker to cause a denial of service condition by sending a series of specific CIP-based commands to the controller.
CVE-2022-3752 1 Rockwellautomation 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more 2024-08-03 8.6 High
An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation.
CVE-2022-1797 1 Rockwellautomation 18 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 15 more 2024-08-03 6.8 Medium
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.
CVE-2022-1159 1 Rockwellautomation 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more 2024-08-02 7.7 High
Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user.