Filtered by vendor Rockwellautomation
Subscriptions
Filtered by product Compactlogix 5480 Firmware
Subscriptions
Total
7 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2024-6077 | 1 Rockwellautomation | 18 1756-en4, 1756-en4 Firmware, Compact Guardlogix 5380 Sil2 Firmware and 15 more | 2024-09-19 | 7.5 High |
A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover. | ||||
CVE-2022-1161 | 1 Rockwellautomation | 48 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 45 more | 2024-09-16 | 10 Critical |
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other. | ||||
CVE-2024-7507 | 1 Rockwellautomation | 5 Compact Guardlogix 5380 Firmware, Compactlogix 5480 Firmware, Controllogix 5380 Firmware and 2 more | 2024-08-15 | N/A |
CVE-2024-7507 IMPACT A denial-of-service vulnerability exists in the affected products. This vulnerability occurs when a malformed PCCC message is received, causing a fault in the controller. | ||||
CVE-2024-7515 | 1 Rockwellautomation | 5 Compact Guardlogix 5380 Firmware, Compactlogix 5380 Firmware, Compactlogix 5480 Firmware and 2 more | 2024-08-15 | N/A |
CVE-2024-7515 IMPACT A denial-of-service vulnerability exists in the affected products. A malformed PTP management packet can cause a major nonrecoverable fault in the controller. | ||||
CVE-2022-3752 | 1 Rockwellautomation | 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more | 2024-08-03 | 8.6 High |
An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation. | ||||
CVE-2022-1797 | 1 Rockwellautomation | 18 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 15 more | 2024-08-03 | 6.8 Medium |
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online. | ||||
CVE-2022-1159 | 1 Rockwellautomation | 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more | 2024-08-02 | 7.7 High |
Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user. |