Filtered by vendor Siemens
Subscriptions
Filtered by product En100 Ethernet Module Dnp3 Firmware
Subscriptions
Total
4 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2022-30937 | 1 Siemens | 6 En100 Ethernet Module, En100 Ethernet Module Dnp3 Firmware, En100 Ethernet Module Iec 104 Firmware and 3 more | 2024-11-21 | 7.5 High |
A vulnerability has been identified in EN100 Ethernet module DNP3 IP variant (All versions), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). Affected applications contains a memory corruption vulnerability while parsing specially crafted HTTP packets to /txtrace endpoint. This could allow an attacker to crash the affected application leading to a denial of service condition. | ||||
CVE-2018-4840 | 1 Siemens | 17 Digsi 4, En100 Ethernet Module Dnp3, En100 Ethernet Module Dnp3 Firmware and 14 more | 2024-11-21 | N/A |
A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The device engineering mechanism allows an unauthenticated remote user to upload a modified device configuration overwriting access authorization passwords. | ||||
CVE-2018-4839 | 1 Siemens | 17 Digsi 4, En100 Ethernet Module Dnp3, En100 Ethernet Module Dnp3 Firmware and 14 more | 2024-11-21 | N/A |
A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions), Other SIPROTEC 4 relays (All versions), Other SIPROTEC Compact relays (All versions), SIPROTEC 4 7SD80 (All versions < V4.70), SIPROTEC 4 7SJ61 (All versions < V4.96), SIPROTEC 4 7SJ62 (All versions < V4.96), SIPROTEC 4 7SJ64 (All versions < V4.96), SIPROTEC 4 7SJ66 (All versions < V4.30), SIPROTEC Compact 7SJ80 (All versions < V4.77), SIPROTEC Compact 7SK80 (All versions < V4.77). An attacker with local access to the engineering system or in a privileged network position and able to obtain certain network traffic could possibly reconstruct access authorization passwords. | ||||
CVE-2018-4838 | 1 Siemens | 10 En100 Ethernet Module Dnp3, En100 Ethernet Module Dnp3 Firmware, En100 Ethernet Module Iec 104 and 7 more | 2024-11-21 | N/A |
A vulnerability has been identified in EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module DNP3 variant (All versions < V1.04), EN100 Ethernet module PROFINET IO variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module IEC 104 variant (All versions < V1.22). The web interface (TCP/80) of affected devices allows an unauthenticated user to upgrade or downgrade the firmware of the device, including to older versions with known vulnerabilities. |
Page 1 of 1.