Filtered by vendor Omron Subscriptions
Filtered by product Nj101-1000 Firmware Subscriptions
Total 6 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2024-33687 1 Omron 110 Nj-pa3001, Nj-pa3001 Firmware, Nj-pd3001 and 107 more 2024-11-21 7.5 High
Insufficient verification of data authenticity issue exists in NJ Series CPU Unit all versions and NX Series CPU Unit all versions. If a user program in the affected product is altered, the product may not be able to detect the alteration.
CVE-2023-27396 1 Omron 542 Cj2h-cpu64, Cj2h-cpu64-eip, Cj2h-cpu64-eip Firmware and 539 more 2024-11-21 9.8 Critical
FINS (Factory Interface Network Service) is a message communication protocol, which is designed to be used in closed FA (Factory Automation) networks, and is used in FA networks composed of OMRON products. Multiple OMRON products that implement FINS protocol contain following security issues -- (1)Plaintext communication, and (2)No authentication required. When FINS messages are intercepted, the contents may be retrieved. When arbitrary FINS messages are injected, any commands may be executed on, or the system information may be retrieved from, the affected device. Affected products and versions are as follows: SYSMAC CS-series CPU Units, all versions, SYSMAC CJ-series CPU Units, all versions, SYSMAC CP-series CPU Units, all versions, SYSMAC NJ-series CPU Units, all versions, SYSMAC NX1P-series CPU Units, all versions, SYSMAC NX102-series CPU Units, all versions, and SYSMAC NX7 Database Connection CPU Units (Ver.1.16 or later)
CVE-2022-34151 1 Omron 113 Na5-12w, Na5-12w Firmware, Na5-15w and 110 more 2024-11-21 8.1 High
Use of hard-coded credentials vulnerability exists in Machine automation controller NJ series all models V 1.48 and earlier, Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, Automation software 'Sysmac Studio' all models V1.49 and earlier, and Programmable Terminal (PT) NA series NA5-15W/NA5-12W/NA5-9W/NA5-7W models Runtime V1.15 and earlier, which may allow a remote attacker who successfully obtained the user credentials by analyzing the affected product to access the controller.
CVE-2022-33971 1 Omron 104 Nj-pa3001, Nj-pa3001 Firmware, Nj-pd3001 and 101 more 2024-11-21 7.5 High
Authentication bypass by capture-replay vulnerability exists in Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, and Machine automation controller NJ series all models V 1.48 and earlier, which may allow an adjacent attacker who can analyze the communication between the controller and the specific software used by OMRON internally to cause a denial-of-service (DoS) condition or execute a malicious program.
CVE-2022-33208 1 Omron 113 Na5-12w, Na5-12w Firmware, Na5-15w and 110 more 2024-11-21 8.1 High
Authentication bypass by capture-replay vulnerability exists in Machine automation controller NJ series all models V 1.48 and earlier, Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, Automation software 'Sysmac Studio' all models V1.49 and earlier, and Programmable Terminal (PT) NA series NA5-15W/NA5-12W/NA5-9W/NA5-7W models Runtime V1.15 and earlier, which may allow a remote attacker who can analyze the communication between the affected controller and automation software 'Sysmac Studio' and/or a Programmable Terminal (PT) to access the controller.
CVE-2022-31206 1 Omron 50 Nj101-1000, Nj101-1000 Firmware, Nj101-1020 and 47 more 2024-11-21 9.8 Critical
The Omron SYSMAC Nx product family PLCs (NJ series, NY series, NX series, and PMAC series) through 2022-005-18 lack cryptographic authentication. These PLCs are programmed using the SYMAC Studio engineering software (which compiles IEC 61131-3 conformant POU code to native machine code for execution by the PLC's runtime). The resulting machine code is executed by a runtime, typically controlled by a real-time operating system. The logic that is downloaded to the PLC does not seem to be cryptographically authenticated, allowing an attacker to manipulate transmitted object code to the PLC and execute arbitrary machine code on the processor of the PLC's CPU module in the context of the runtime. In the case of at least the NJ series, an RTOS and hardware combination is used that would potentially allow for memory protection and privilege separation and thus limit the impact of code execution. However, it was not confirmed whether these sufficiently segment the runtime from the rest of the RTOS.