Search
Search Results (13 CVEs found)
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2010-5305 | 1 Rockwellautomation | 5 Plc5 1785-lx, Plc5 1785-lx Firmware, Rslogix and 2 more | 2025-06-26 | N/A |
The potential exists for exposure of the product's password used to restrict unauthorized access to Rockwell PLC5/SLC5/0x/RSLogix 1785-Lx and 1747-L5x controllers. The potential exists for an unauthorized programming and configuration client to gain access to the product and allow changes to the product’s configuration or program. When applicable, upgrade product firmware to a version that includes enhanced security functionality compatible with Rockwell Automation's FactoryTalk Security services. | ||||
CVE-2016-9343 | 1 Rockwellautomation | 32 1768 Compact Guardlogix L4xs Controller, 1768 Compact Guardlogix L4xs Controller Firmware, 1768 Compactlogix L4x Controller and 29 more | 2025-04-20 | 10.0 Critical |
An issue was discovered in Rockwell Automation Logix5000 Programmable Automation Controller FRN 16.00 through 21.00 (excluding all firmware versions prior to FRN 16.00, which are not affected). By sending malformed common industrial protocol (CIP) packet, an attacker may be able to overflow a stack-based buffer and execute code on the controller or initiate a nonrecoverable fault resulting in a denial of service. | ||||
CVE-2016-5814 | 1 Rockwellautomation | 5 Rslogix 500 Professional Edition, Rslogix 500 Standard Edition, Rslogix 500 Starter Edition and 2 more | 2025-04-12 | N/A |
Buffer overflow in Rockwell Automation RSLogix Micro Starter Lite, RSLogix Micro Developer, RSLogix 500 Starter Edition, RSLogix 500 Standard Edition, and RSLogix 500 Professional Edition allows remote attackers to execute arbitrary code via a crafted RSS project file. | ||||
CVE-2012-0221 | 1 Rockwellautomation | 2 Factorytalk, Rslogix 5000 | 2025-04-11 | N/A |
The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 does not properly handle the return value from an unspecified function, which allows remote attackers to cause a denial of service (service outage) via a crafted packet. | ||||
CVE-2011-3489 | 1 Rockwellautomation | 1 Rslogix | 2025-04-11 | N/A |
RnaUtility.dll in RsvcHost.exe 2.30.0.23 in Rockwell RSLogix 19 and earlier allows remote attackers to cause a denial of service (crash) via a crafted rna packet with a long string to TCP port 4446 that triggers (1) "a memset zero overflow" or (2) an out-of-bounds read, related to improper handling of a 32-bit size field. | ||||
CVE-2012-0222 | 1 Rockwellautomation | 2 Factorytalk, Rslogix 5000 | 2025-04-11 | N/A |
The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 allows remote attackers to cause a denial of service (out-of-bounds read) via a crafted packet. | ||||
CVE-2014-0755 | 1 Rockwellautomation | 2 Logix 5000 Controller, Rslogix 5000 Design And Configuration Software | 2025-04-11 | N/A |
Rockwell Automation RSLogix 5000 7 through 20.01, and 21.0, does not properly implement password protection for .ACD files (aka project files), which allows local users to obtain sensitive information or modify data via unspecified vectors. | ||||
CVE-2021-22681 | 1 Rockwellautomation | 20 Compact Guardlogix 5370, Compact Guardlogix 5380, Compactlogix 1768 and 17 more | 2024-11-21 | 9.8 Critical |
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. | ||||
CVE-2020-6990 | 1 Rockwellautomation | 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more | 2024-11-21 | 9.8 Critical |
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller. | ||||
CVE-2020-6988 | 1 Rockwellautomation | 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more | 2024-11-21 | 7.5 High |
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials. | ||||
CVE-2020-6984 | 1 Rockwellautomation | 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more | 2024-11-21 | 7.5 High |
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable. | ||||
CVE-2020-6980 | 1 Rockwellautomation | 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more | 2024-11-21 | 3.3 Low |
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, If Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim’s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext. | ||||
CVE-2024-7847 | 1 Rockwellautomation | 4 Rslogix 5, Rslogix 500, Rslogix Micro Developer and 1 more | 2024-10-15 | 7.7 High |
VULNERABILITY DETAILS Rockwell Automation used the latest versions of the CVSS scoring system to assess the following vulnerabilities. The following vulnerabilities were reported to us by Sharon Brizinov of Claroty Research - Team82. A feature in the affected products enables users to prepare a project file with an embedded VBA script and can be configured to run once the project file has been opened without user intervention. This feature can be abused to trick a legitimate user into executing malicious code upon opening an infected RSP/RSS project file. If exploited, a threat actor may be able to perform a remote code execution. Connected devices may also be impacted by exploitation of this vulnerability. |
Page 1 of 1.