Filtered by vendor Rockwellautomation Subscriptions
Filtered by product Rslogix 500 Subscriptions
Total 5 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2024-7847 1 Rockwellautomation 4 Rslogix 5, Rslogix 500, Rslogix Micro Developer and 1 more 2024-10-15 7.7 High
VULNERABILITY DETAILS Rockwell Automation used the latest versions of the CVSS scoring system to assess the following vulnerabilities. The following vulnerabilities were reported to us by Sharon Brizinov of Claroty Research - Team82. A feature in the affected products enables users to prepare a project file with an embedded VBA script and can be configured to run once the project file has been opened without user intervention. This feature can be abused to trick a legitimate user into executing malicious code upon opening an infected RSP/RSS project file. If exploited, a threat actor may be able to perform a remote code execution. Connected devices may also be impacted by exploitation of this vulnerability.
CVE-2020-6980 1 Rockwellautomation 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more 2024-08-04 3.3 Low
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, If Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim’s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext.
CVE-2020-6984 1 Rockwellautomation 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more 2024-08-04 7.5 High
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable.
CVE-2020-6990 1 Rockwellautomation 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more 2024-08-04 9.8 Critical
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller.
CVE-2020-6988 1 Rockwellautomation 6 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 3 more 2024-08-04 7.5 High
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials.