Filtered by vendor Siemens
Subscriptions
Filtered by product Simatic Et 200 Open Controller Cpu 1515sp Pc2
Subscriptions
Total
2 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2019-6575 | 1 Siemens | 43 Opc Unified Architecture, Simatic Cp443-1 Opc Ua, Simatic Cp443-1 Opc Ua Firmware and 40 more | 2024-08-04 | 7.5 High |
A vulnerability has been identified in SIMATIC CP 443-1 OPC UA (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V2.7), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Upd 4), SIMATIC IPC DiagMonitor (All versions < V5.1.3), SIMATIC NET PC Software V13 (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC RF188C (All versions < V1.1.0), SIMATIC RF600R family (All versions < V3.2.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.5 < V2.6.1), SIMATIC S7-1500 Software Controller (All versions between V2.5 (including) and V2.7 (excluding)), SIMATIC WinCC OA (All versions < V3.15 P018), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Upd 4), SINEC NMS (All versions < V1.0 SP1), SINEMA Server (All versions < V14 SP2), SINUMERIK OPC UA Server (All versions < V2.1), TeleControl Server Basic (All versions < V3.1.1). Specially crafted network packets sent to affected devices on port 4840/tcp could allow an unauthenticated remote attacker to cause a denial of service condition of the OPC communication or crash the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the OPC communication. | ||||
CVE-2022-38465 | 1 Siemens | 89 Simatic Drive Controller Cpu 1504d Tf, Simatic Drive Controller Cpu 1504d Tf Firmware, Simatic Drive Controller Cpu 1507d Tf and 86 more | 2024-08-03 | 9.3 Critical |
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINUMERIK MC (All versions < V6.21), SINUMERIK ONE (All versions < V6.21). Affected products protect the built-in global private key in a way that cannot be considered sufficient any longer. The key is used for the legacy protection of confidential configuration data and the legacy PG/PC and HMI communication. This could allow attackers to discover the private key of a CPU product family by an offline attack against a single CPU of the family. Attackers could then use this knowledge to extract confidential configuration data from projects that are protected by that key or to perform attacks against legacy PG/PC and HMI communication. |
Page 1 of 1.