Search Results (11 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2019-19300 1 Siemens 65 Ktk Ate530s, Ktk Ate530s Firmware, Sidoor Atd430w and 62 more 2025-07-08 7.5 High
A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P, KTK ATE530S, SIDOOR ATD430W, SIDOOR ATE530S COATED, SIDOOR ATE531S, SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0), SIMATIC ET 200eco PN, AI 8xRTD/TC, M12-L (6ES7144-6JF00-0BB0), SIMATIC ET 200eco PN, CM 4x IO-Link, M12-L (6ES7148-6JE00-0BB0), SIMATIC ET 200eco PN, CM 8x IO-Link, M12-L (6ES7148-6JG00-0BB0), SIMATIC ET 200eco PN, CM 8x IO-Link, M12-L (6ES7148-6JJ00-0BB0), SIMATIC ET 200eco PN, DI 16x24VDC, M12-L (6ES7141-6BH00-0BB0), SIMATIC ET 200eco PN, DI 8x24VDC, M12-L (6ES7141-6BG00-0BB0), SIMATIC ET 200eco PN, DIQ 16x24VDC/2A, M12-L (6ES7143-6BH00-0BB0), SIMATIC ET 200eco PN, DQ 8x24VDC/0,5A, M12-L (6ES7142-6BG00-0BB0), SIMATIC ET 200eco PN, DQ 8x24VDC/2A, M12-L (6ES7142-6BR00-0BB0), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0), SIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0), SIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0), SIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0), SIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0), SIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants), SIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants), SIMATIC MICRO-DRIVE PDC, SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants), SIMATIC S7-1500 CPU family (incl. related ET 200 CPUs and SIPLUS variants), SIMATIC S7-1500 Software Controller, SIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0), SIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0), SIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0), SIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0), SIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0), SIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0), SIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0), SIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0), SIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0), SIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0), SIMATIC S7-400 H V6 and below CPU family (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants), SIMATIC TDC CP51M1, SIMATIC TDC CPU555, SIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0), SIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0), SINAMICS S/G Control Unit w. PROFINET, SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0), SIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0), SIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0), SIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0), SIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0), SIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0), SIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0), SIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0). The Interniche-based TCP Stack can be forced to make very expensive calls for every incoming packet which can lead to a denial of service.
CVE-2022-25622 1 Siemens 23 Simatic Cfu Diq, Simatic Cfu Diq Firmware, Simatic Cfu Pa and 20 more 2025-04-21 5.3 Medium
The PROFINET (PNIO) stack, when integrated with the Interniche IP stack, improperly handles internal resources for TCP segments where the minimum TCP-Header length is less than defined. This could allow an attacker to create a denial of service condition for TCP services on affected devices by sending specially crafted TCP segments.
CVE-2015-2177 1 Siemens 2 Simatic S7-300 Cpu, Simatic S7-300 Cpu Firmware 2025-04-12 N/A
Siemens SIMATIC S7-300 CPU devices allow remote attackers to cause a denial of service (defect-mode transition) via crafted packets on (1) TCP port 102 or (2) Profibus.
CVE-2016-9159 1 Siemens 21 Simatic S7-300 Cpu 312, Simatic S7-300 Cpu 314, Simatic S7-300 Cpu 315-2 Dp and 18 more 2025-04-12 N/A
A vulnerability has been identified in SIMATIC S7-300 CPU family (All versions), SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 V6 and earlier CPU family (All versions), SIMATIC S7-400 V7 CPU family (All versions), SIMATIC S7-410 V8 CPU family (All versions), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions). An attacker with network access to port 102/tcp (ISO-TSAP) or via Profibus could obtain credentials from the PLC if protection-level 2 is configured on the affected devices.
CVE-2016-9158 1 Siemens 21 Simatic S7-300 Cpu 312, Simatic S7-300 Cpu 314, Simatic S7-300 Cpu 315-2 Dp and 18 more 2025-04-12 N/A
A vulnerability has been identified in SIMATIC S7-300 CPU family (All versions), SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 V6 and earlier CPU family (All versions), SIMATIC S7-400 V7 CPU family (All versions). Specially crafted packets sent to port 80/tcp could cause the affected devices to go into defect mode. A cold restart is required to recover the system.
CVE-2019-10923 1 Siemens 78 Cp1604, Cp1604 Firmware, Cp1616 and 75 more 2025-02-11 7.5 High
An attacker with network access to an affected product may cause a denial of service condition by breaking the real-time synchronization (IRT) of the affected installation.
CVE-2020-15791 1 Siemens 28 Simatic S7-300 Cpu 312, Simatic S7-300 Cpu 312 Firmware, Simatic S7-300 Cpu 314 and 25 more 2024-11-21 6.5 Medium
A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 CPU family (incl. SIPLUS variants) (All versions), SIMATIC WinAC RTX (F) 2010 (All versions), SINUMERIK 840D sl (All versions). The authentication protocol between a client and a PLC via port 102/tcp (ISO-TSAP) insufficiently protects the transmitted password. This could allow an attacker that is able to intercept the network traffic to obtain valid PLC credentials.
CVE-2020-15783 1 Siemens 24 Simatic S7-300 Cpu 312, Simatic S7-300 Cpu 312 Firmware, Simatic S7-300 Cpu 314 and 21 more 2024-11-21 7.5 High
A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC TDC CPU555 (All versions), SINUMERIK 840D sl (All versions). Sending multiple specially crafted packets to the affected devices could cause a Denial-of-Service on port 102. A cold restart is required to recover the service.
CVE-2019-18336 1 Siemens 23 Simatic S7-300 Cpu, Simatic S7-300 Cpu 312 Ifm, Simatic S7-300 Cpu 312 Ifm Firmware and 20 more 2024-11-21 7.5 High
A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V3.X.17), SIMATIC TDC CP51M1 (All versions < V1.1.8), SIMATIC TDC CPU555 (All versions < V1.1.1), SINUMERIK 840D sl (All versions < V4.8.6), SINUMERIK 840D sl (All versions < V4.94). Specially crafted packets sent to port 102/tcp (Profinet) could cause the affected device to go into defect mode. A restart is required in order to recover the system. Successful exploitation requires an attacker to have network access to port 102/tcp, with no authentication. No user interation is required. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-13940 1 Siemens 47 S7-1200 Cpu 1211c, S7-1200 Cpu 1211c Firmware, S7-1200 Cpu 1212c and 44 more 2024-11-21 5.3 Medium
A vulnerability has been identified in SIMATIC ET 200pro IM154-8 PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200pro IM154-8F PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200pro IM154-8FX PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200S IM151-8 PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200S IM151-8F PN/DP CPU (All versions < V3.X.17), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.1), SIMATIC S7-300 CPU 314C-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315F-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315T-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317F-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317T-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317TF-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 319-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 319F-3 PN/DP (All versions < V3.X.17), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC WinAC RTX 2010 (All versions), SIMATIC WinAC RTX F 2010 (All versions), SIPLUS ET 200S IM151-8 PN/DP CPU (All versions < V3.X.17), SIPLUS ET 200S IM151-8F PN/DP CPU (All versions < V3.X.17), SIPLUS S7-300 CPU 314C-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 315-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 315F-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 317-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 317F-2 PN/DP (All versions < V3.X.17). Affected devices contain a vulnerability that could cause a denial of service condition of the web server by sending specially crafted HTTP requests to ports 80/tcp and 443/tcp. Beyond the web service, no other functions or interfaces are affected by the denial of service condition.
CVE-2019-10936 1 Siemens 130 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 and 127 more 2024-11-21 7.5 High
Affected devices improperly handle large amounts of specially crafted UDP packets. This could allow an unauthenticated remote attacker to trigger a denial of service condition.