CVE-2020-15783 | 1 Siemens | 24 Simatic S7-300 Cpu 312, Simatic S7-300 Cpu 312 Firmware, Simatic S7-300 Cpu 314 and 21 more | 2024-11-21 | 7.5 High |
A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC TDC CPU555 (All versions), SINUMERIK 840D sl (All versions). Sending multiple specially crafted packets to the affected devices could cause a Denial-of-Service on port 102. A cold restart is required to recover the service. | ||||
CVE-2018-11464 | 1 Siemens | 4 Sinumerik 828d, Sinumerik 828d Firmware, Sinumerik 840d Sl and 1 more | 2024-11-21 | N/A |
A vulnerability has been identified in SINUMERIK 828D V4.7 (All versions < V4.7 SP6 HF1), SINUMERIK 840D sl V4.7 (All versions < V4.7 SP6 HF5), SINUMERIK 840D sl V4.8 (All versions < V4.8 SP3). The integrated VNC server on port 5900/tcp of the affected products could allow a remote attacker to cause a Denial-of-Service condition of the VNC server. Please note that this vulnerability is only exploitable if port 5900/tcp is manually opened in the firewall configuration of network port X130. The security vulnerability could be exploited by an attacker with network access to the affected devices and port. Successful exploitation requires no privileges and no user interaction. The vulnerability could allow an attacker to compromise availability of the VNC server. At the time of advisory publication no public exploitation of this security vulnerability was known. | ||||
CVE-2017-2681 | 1 Siemens | 155 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 Pn Io and 152 more | 2024-11-21 | 6.5 Medium |
Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. | ||||
CVE-2017-2680 | 1 Siemens | 183 S110 Pn, Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware and 180 more | 2024-11-21 | 6.5 Medium |
Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected. | ||||
CVE-2017-12741 | 1 Siemens | 76 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200p and 73 more | 2024-11-21 | 7.5 High |
Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually. | ||||
CVE-2024-41171 | 1 Siemens | 3 Sinumerik 828d Firmware, Sinumerik 840d Sl Firmware, Sinumerik One Firmware | 2024-09-10 | 8.8 High |
A vulnerability has been identified in SINUMERIK 828D V4 (All versions), SINUMERIK 828D V5 (All versions < V5.24), SINUMERIK 840D sl V4 (All versions), SINUMERIK ONE (All versions < V6.24). Affected devices do not properly enforce access restrictions to scripts that are regularly executed by the system with elevated privileges. This could allow an authenticated local attacker to escalate their privileges in the underlying system. |