An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0028 Fault Type: Non-User Description: Values 0x01 and 0x02 are invalid values for the user fault routine. By writing directly to the file it is possible to set these values. When this is done and the device is moved into a run state, a fault is triggered. NOTE: This is not possible through RSLogix.
History

No history.

cve-icon MITRE

Status: PUBLISHED

Assigner: talos

Published: 2018-04-05T21:00:00Z

Updated: 2024-09-16T17:48:19.444Z

Reserved: 2017-09-13T00:00:00

Link: CVE-2017-14469

cve-icon Vulnrichment

No data.

cve-icon NVD

Status : Modified

Published: 2018-04-05T21:29:00.977

Modified: 2024-11-21T03:12:51.330

Link: CVE-2017-14469

cve-icon Redhat

No data.