A vulnerability has been identified in APOGEE MBC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE MEC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE PXC Compact (BACnet) (All versions < V3.5.3), APOGEE PXC Compact (P2 Ethernet) (All versions >= V2.8), APOGEE PXC Modular (BACnet) (All versions < V3.5.3), APOGEE PXC Modular (P2 Ethernet) (All versions >= V2.8), TALON TC Compact (BACnet) (All versions < V3.5.3), TALON TC Modular (BACnet) (All versions < V3.5.3). The web server of affected devices lacks proper bounds checking when parsing the Host parameter in HTTP requests, which could lead to a buffer overflow. An unauthenticated remote attacker could exploit this vulnerability to execute arbitrary code on the device with root privileges.
Fixes

Solution

No solution given by the vendor.


Workaround

No workaround given by the vendor.

History

Thu, 24 Apr 2025 20:15:00 +0000

Type Values Removed Values Added
Metrics ssvc

{'options': {'Automatable': 'yes', 'Exploitation': 'none', 'Technical Impact': 'total'}, 'version': '2.0.3'}


cve-icon MITRE

Status: PUBLISHED

Assigner: siemens

Published:

Updated: 2025-04-23T19:28:38.162Z

Reserved: 2021-02-18T00:00:00.000Z

Link: CVE-2021-27391

cve-icon Vulnrichment

Updated: 2024-08-03T20:48:16.974Z

cve-icon NVD

Status : Modified

Published: 2021-09-14T11:15:23.913

Modified: 2025-04-23T20:15:22.940

Link: CVE-2021-27391

cve-icon Redhat

No data.

cve-icon OpenCVE Enrichment

No data.