Metrics
Affected Vendors & Products
Source | ID | Title |
---|---|---|
![]() |
EUVD-2022-24770 | Windows OS can be configured to overlay a “language bar” on top of any application. When this OS functionality is enabled, the OS language bar UI will be viewable in the browser alongside the AVEVA InTouch Access Anywhere and Plant SCADA Access Anywhere applications. It is possible to manipulate the Windows OS language bar to launch an OS command prompt, resulting in a context-escape from application into OS. |
Solution
No solution given by the vendor.
Workaround
AVEVA recommends the following mitigations: Disable the Windows language bar on the server machine hosting InTouch Access Anywhere and Plant SCADA Access Anywhere applications unless it is required. Create unique user accounts with minimal privileges dedicated only to remote access of InTouch Access Anywhere and Plant SCADA Access Anywhere applications. Utilize OS group policy objects (GPOs) to further restrict what those unique user accounts are allowed to do. Restrict access based on Microsoft’s recommended block list. For more information on this vulnerability, including security updates, please see security bulletin AVEVA-2022-001
Wed, 16 Apr 2025 17:15:00 +0000
Type | Values Removed | Values Added |
---|---|---|
Metrics |
ssvc
|

Status: PUBLISHED
Assigner: icscert
Published:
Updated: 2025-04-16T16:19:11.145Z
Reserved: 2022-04-25T00:00:00.000Z
Link: CVE-2022-1467

Updated: 2024-08-03T00:03:06.203Z

Status : Modified
Published: 2022-05-23T20:16:40.833
Modified: 2024-11-21T06:40:46.820
Link: CVE-2022-1467

No data.

No data.