The Motorola ACE1000 RTU through 2022-05-02 has default credentials. It exposes an SSH interface on port 22/TCP. This interface is used for remote maintenance and for SFTP file-transfer operations that are part of engineering software functionality. Access to this interface is controlled by 5 preconfigured accounts (root, abuilder, acelogin, cappl, ace), all of which come with default credentials. Although the ACE1000 documentation mentions the root, abuilder and acelogin accounts and instructs users to change the default credentials, the cappl and ace accounts remain undocumented and thus are unlikely to have their credentials changed.
Metrics
Affected Vendors & Products
Advisories
Source | ID | Title |
---|---|---|
![]() |
EUVD-2022-52225 | The Motorola ACE1000 RTU through 2022-05-02 has default credentials. It exposes an SSH interface on port 22/TCP. This interface is used for remote maintenance and for SFTP file-transfer operations that are part of engineering software functionality. Access to this interface is controlled by 5 preconfigured accounts (root, abuilder, acelogin, cappl, ace), all of which come with default credentials. Although the ACE1000 documentation mentions the root, abuilder and acelogin accounts and instructs users to change the default credentials, the cappl and ace accounts remain undocumented and thus are unlikely to have their credentials changed. |
Fixes
Solution
No solution given by the vendor.
Workaround
No workaround given by the vendor.
References
History
No history.

Status: PUBLISHED
Assigner: mitre
Published:
Updated: 2024-08-03T06:48:34.779Z
Reserved: 2022-05-04T00:00:00
Link: CVE-2022-30270

No data.

Status : Modified
Published: 2022-07-26T23:15:08.137
Modified: 2024-11-21T07:02:28.067
Link: CVE-2022-30270

No data.

No data.