The Motorola MOSCAD and ACE line of RTUs through 2022-05-02 omit an authentication requirement. They feature IP Gateway modules which allow for interfacing between Motorola Data Link Communication (MDLC) networks (potentially over a variety of serial, RF and/or Ethernet links) and TCP/IP networks. Communication with RTUs behind the gateway is done by means of the proprietary IPGW protocol (5001/TCP). This protocol does not have any authentication features, allowing any attacker capable of communicating with the port in question to invoke (a subset of) desired functionality.
Advisories

No advisories yet.

Fixes

Solution

No solution given by the vendor.


Workaround

No workaround given by the vendor.

History

No history.

cve-icon MITRE

Status: PUBLISHED

Assigner: mitre

Published:

Updated: 2024-08-03T06:48:35.991Z

Reserved: 2022-05-04T00:00:00

Link: CVE-2022-30276

cve-icon Vulnrichment

No data.

cve-icon NVD

Status : Modified

Published: 2022-07-26T23:15:08.293

Modified: 2024-11-21T07:02:28.993

Link: CVE-2022-30276

cve-icon Redhat

No data.

cve-icon OpenCVE Enrichment

No data.