Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Advisories

No advisories yet.

Fixes

Solution

No solution given by the vendor.


Workaround

No workaround given by the vendor.

History

Wed, 20 Nov 2024 17:15:00 +0000

Type Values Removed Values Added
Metrics ssvc

{'options': {'Automatable': 'no', 'Exploitation': 'none', 'Technical Impact': 'total'}, 'version': '2.0.3'}


cve-icon MITRE

Status: PUBLISHED

Assigner: mitre

Published:

Updated: 2024-11-20T16:16:57.817Z

Reserved: 2022-05-06T00:00:00

Link: CVE-2022-30319

cve-icon Vulnrichment

Updated: 2024-08-03T06:48:36.317Z

cve-icon NVD

Status : Modified

Published: 2022-07-28T16:15:11.500

Modified: 2024-11-21T07:02:34.433

Link: CVE-2022-30319

cve-icon Redhat

No data.

cve-icon OpenCVE Enrichment

No data.