Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Metrics
Affected Vendors & Products
References
History
Wed, 20 Nov 2024 17:15:00 +0000
Type | Values Removed | Values Added |
---|---|---|
Metrics |
ssvc
|
MITRE
Status: PUBLISHED
Assigner: mitre
Published: 2022-07-28T15:50:53
Updated: 2024-11-20T16:16:57.817Z
Reserved: 2022-05-06T00:00:00
Link: CVE-2022-30319
Vulnrichment
Updated: 2024-08-03T06:48:36.317Z
NVD
Status : Modified
Published: 2022-07-28T16:15:11.500
Modified: 2024-11-21T07:02:34.433
Link: CVE-2022-30319
Redhat
No data.