Description
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The affected product web service does not properly validate the length of user-controllable input. This could allow an unauthenticated remote attacker to read portions of device memory or to cause a denial-of-service condition.
Published: 2026-10-13
Score: 8.8 High
EPSS: < 1% Very Low
KEV: No
Impact: Remote Memory Read / Denial of Service
Action: Patch Promptly
AI Analysis

Impact

The vulnerability stems from the Siemens APOGEE device web service failing to validate the length of user‑controllable input. Because the input length is unchecked, a crafted request can trigger an overflow or other memory corruption that allows an attacker without authentication to read arbitrary portions of the device’s memory or to exhaust resources and force the service to crash. Based on the description, it is inferred that the lack of validation could lead to an integer overflow or buffer overflow, which is why the weakness is identified as CWE‑191.

Affected Systems

Affected products are Siemens APOGEE MBC (PPC) for BACnet and P2 Ethernet, Siemens APOGEE MEC (PPC) for BACnet and P2 Ethernet, Siemens APOGEE PXC Compact for BACnet versions lower than 3.5.7 and for P2 Ethernet versions lower than 2.8.21, Siemens APOGEE PXC Modular for BACnet lower than 3.5.7 and for P2 Ethernet lower than 2.8.21, Siemens TALON TC Compact for BACnet versions lower than 3.5.7, and Siemens TALON TC Modular for BACnet lower than 3.5.7. No versions are listed as having the input‑length validation fix, so all of the stated versions are considered vulnerable.

Risk and Exploitability

The CVSS base score is 8.8, indicating high severity. No EPSS score is available, and the issue is not yet listed in the CISA KEV catalog. The likely attack vector is an unauthenticated network attacker who can send malformed requests over an exposed BACnet or P2 Ethernet interface; this is inferred from the description that the flaw is triggered by user‑controlled input received over those protocols. Exploiting the bug requires only network connectivity to the affected interface and does not require authentication, making the vulnerability readily exploitable in realistic operational environments.

Generated by OpenCVE AI on October 13, 2026 at 11:12 UTC.

Remediation

No solution or workaround provided in the CVE record.

OpenCVE Recommended Actions

  • Apply the latest Siemens firmware that includes the input‑length validation fix; for example, upgrade APOGEE PXC Compact to version 3.5.7 or later, or upgrade any other affected product to the most recent release.
  • If an update is not immediately available, restrict network exposure by placing the device in a segregated segment or applying firewall rules that limit BACnet and P2 Ethernet traffic to trusted hosts only.
  • Enable detailed logging on the device and configure alerts for repeated malformed requests or crashes, which may indicate ongoing exploitation attempts.

Generated by OpenCVE AI on October 13, 2026 at 11:12 UTC.

Tracking

Sign in to view the affected projects.

Advisories

No advisories yet.

History

Wed, 14 Oct 2026 20:30:00 +0000

Type Values Removed Values Added
Metrics ssvc

{'options': {'Automatable': 'yes', 'Exploitation': 'none', 'Technical Impact': 'partial'}, 'version': '2.0.3'}


Tue, 13 Oct 2026 11:30:00 +0000

Type Values Removed Values Added
Title Unvalidated Input in Siemens APOGEE Web Service Enables Unauthenticated Remote Memory Read or Denial of Service

Tue, 13 Oct 2026 09:45:00 +0000

Type Values Removed Values Added
Description A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The affected product web service does not properly validate the length of user-controllable input. This could allow an unauthenticated remote attacker to read portions of device memory or to cause a denial-of-service condition.
Weaknesses CWE-191
References
Metrics cvssV3_1

{'score': 8.2, 'vector': 'CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:L'}

cvssV4_0

{'score': 8.8, 'vector': 'CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:L/SC:N/SI:N/SA:N'}


Subscriptions

No data.

cve-icon MITRE

Status: PUBLISHED

Assigner: siemens

Published:

Updated: 2026-10-14T19:29:28.638Z

Reserved: 2026-09-28T17:37:23.337Z

Link: CVE-2026-102073

cve-icon Vulnrichment

Updated: 2026-10-14T19:29:24.819Z

cve-icon NVD

Status : Awaiting Analysis

Published: 2026-10-13T10:17:14.157

Modified: 2026-10-15T20:38:04.303

Link: CVE-2026-102073

cve-icon Redhat

No data.

cve-icon OpenCVE Enrichment

Updated: 2026-10-13T11:15:12Z

Weaknesses
  • CWE-191

    Integer Underflow (Wrap or Wraparound)