CVE-2026-111734

Missing length validation of EtherType, VLAN and FrameID fields in pf_eth_recv()

Published Oct 29, 2026 CVSS 4.0 · 7.1 High EPSS < 1% KEV · Not listed
Description
P-Net before 1.0.3 does not validate the length of a received Ethernet frame in pf_eth_recv() before reading the EtherType, any VLAN tags and the PROFINET FrameID. The VLAN tag loop had no upper bound, so a truncated frame, or a frame consisting only of VLAN tags, makes the function read past the end of the receive buffer. This can cause a crash (denial of service) or disclose memory content.

Analysis

AI-generated

Technical impact

The flaw arises because P‑Net’s Ethernet frame handling routine does not check the length of the received frame before accessing the EtherType, VLAN tag, and PROFINET FrameID fields. An attacker can send a truncated packet or a packet composed only of VLAN tags, causing the code to read past the end of the receive buffer. This leads to an application crash, which results in a denial of service, or it can leak memory contents, allowing information disclosure.

Affected Systems

RT‑Labs P‑Net devices running firmware versions earlier than 1.0.3 are affected. The vulnerability exists in the Ethernet reception module of the firmware and thus impacts all network interfaces on the device.

Risk and Exploitability

The CVSS score of 7.1 indicates a high severity. The EPSS score is unavailable, so the exact likelihood of exploitation cannot be quantified, but the practicality of sending malformed Ethernet frames over the network makes the attack feasible for an adversary with network access. The vulnerability is not listed in the CISA KEV catalog, but it can still be leveraged for denial‑of‑service or data‑leak attacks through crafted network traffic.

Remediation

Vendor Solution

Upgrade to P-Net 1.0.3 or later.


OpenCVE Recommended Actions

  • Upgrade the device firmware to version 1.0.3 or later as advised by RT‑Labs
  • Deploy perimeter network filters or ACLs to block or drop malformed frames that could trigger the overflow, such as those lacking proper length or composed solely of VLAN tags
  • If a quick firmware upgrade is not possible, restrict device access to trusted networks and monitor for abnormal traffic patterns that may indicate exploitation attempts

Generated by OpenCVE AI on October 29, 2026 at 16:32 UTC.

Tracking

Sign in to view the affected projects.

Advisories

No advisories available
History
Type Values Removed Values Added
Metrics ssvc

{'options': {'Automatable': 'no', 'Exploitation': 'none', 'Technical Impact': 'partial'}, 'version': '2.0.3'}

Type Values Removed Values Added
First Time appeared Rt-labs
Rt-labs p-net
Vendors & Products Rt-labs
Rt-labs p-net
Type Values Removed Values Added
Description P-Net before 1.0.3 does not validate the length of a received Ethernet frame in pf_eth_recv() before reading the EtherType, any VLAN tags and the PROFINET FrameID. The VLAN tag loop had no upper bound, so a truncated frame, or a frame consisting only of VLAN tags, makes the function read past the end of the receive buffer. This can cause a crash (denial of service) or disclose memory content.
Title Missing length validation of EtherType, VLAN and FrameID fields in pf_eth_recv()
Weaknesses CWE-125
References
Metrics cvssV4_0

{'score': 7.1, 'vector': 'CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:H/SC:N/SI:N/SA:N'}

Weaknesses

Sources

Status
PUBLISHED
Assigner
rt-labs
Published
Updated
Nov 5, 2026, 9:22 PM
Reserved
Oct 16, 2026, 3:50 PM
Status
Deferred
Published
Oct 29, 2026, 4:17 PM
Modified
Nov 5, 2026, 10:17 PM