Description
Affected devices do not properly sanitize signal names contained in imported CSV trace files before rendering them in selection menus on the Trace page.

This could allow an attacker to social engineer an authorized user who holds the function right “Read diagnostics” into importing a specially crafted trace file. Attacker-controlled JavaScript could be executed in the user’s browser session when the user subsequently interacts with an affected selection menu.
Published: 2026-10-13
Score: 5.3 Medium
EPSS: n/a
KEV: No
Impact: Cross‑Site Scripting via Unsanitized Signal Names
Action: Apply Patch
AI Analysis

Impact

This flaw, a type of unvalidated input leading to client‑side XSS (CWE‑79), causes user‑supplied signal names from imported CSV trace files to be rendered unsanitized, allowing embedded JavaScript to execute when an authorized user with the ‘Read diagnostics’ right interacts with selection menus; this client‑side XSS can result in session hijacking, credential theft, or other malicious actions executed within the user’s browser.

Affected Systems

Siemens SIMATIC Drive Controller CPUs (1504D TF, 1507D TF, 1510SP–1514SP series and variants), ET 200SP CPUs (1510SP–1514SP and Open Controller 1515SP/PC variants, and SIPLUS monitoring units), the S7‑1500 line of CPUs (1511‑1 through 1518‑4, including C‑, F‑, T‑, and TF‑models), SIMATIC S7‑1500 Software Controllers (1507S, 1508S series, Linux V2/V3, and advanced PLCSim models), and SIPLUS S7‑1500 versions are all affected.

Risk and Exploitability

With a CVSS score of 5.3 the vulnerability is of moderate severity. The EPSS score is not available, making precise exploitation probability difficult, and it is not listed in the CISA KEV catalog, indicating no known large‑scale attacks. Nevertheless, the flaw requires social engineering to entice a legitimate user with ‘Read diagnostics’ rights to import a crafted CSV file, which presents a real risk in environments where those permissions are granted.

Generated by OpenCVE AI on October 13, 2026 at 11:17 UTC.

Remediation

No solution or workaround provided in the CVE record.

OpenCVE Recommended Actions

  • Apply the official Siemens firmware update that sanitizes signal names in CSV imports.
  • Restrict the ‘Read diagnostics’ permission to trusted personnel only to reduce the likelihood of an authorized user unknowingly executing malicious code.
  • If a patch is not immediately available, disable importing of CSV trace files or block JavaScript execution in selection menus until a fix is deployed.

Generated by OpenCVE AI on October 13, 2026 at 11:17 UTC.

Tracking

Sign in to view the affected projects.

Advisories

No advisories yet.

History

Tue, 13 Oct 2026 11:45:00 +0000

Type Values Removed Values Added
Title Cross‑Site Scripting via Unsanitized Signal Names in Imported CSV Trace Files

Tue, 13 Oct 2026 09:45:00 +0000

Type Values Removed Values Added
Description Affected devices do not properly sanitize signal names contained in imported CSV trace files before rendering them in selection menus on the Trace page. This could allow an attacker to social engineer an authorized user who holds the function right “Read diagnostics” into importing a specially crafted trace file. Attacker-controlled JavaScript could be executed in the user’s browser session when the user subsequently interacts with an affected selection menu.
Weaknesses CWE-79
References
Metrics cvssV3_1

{'score': 6.1, 'vector': 'CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N'}

cvssV4_0

{'score': 5.3, 'vector': 'CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:P/VC:L/VI:L/VA:N/SC:L/SI:L/SA:N'}


Subscriptions

No data.

cve-icon MITRE

Status: PUBLISHED

Assigner: siemens

Published:

Updated: 2026-10-13T09:18:45.851Z

Reserved: 2026-07-16T14:30:16.083Z

Link: CVE-2026-63355

cve-icon Vulnrichment

No data.

cve-icon NVD

Status : Received

Published: 2026-10-13T10:17:18.870

Modified: 2026-10-13T10:17:18.870

Link: CVE-2026-63355

cve-icon Redhat

No data.

cve-icon OpenCVE Enrichment

Updated: 2026-10-13T11:30:04Z

Weaknesses
  • CWE-79

    Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting')