Filtered by vendor Iconics
Subscriptions
Total
29 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2020-12007 | 2 Iconics, Mitsubishielectric | 11 Bizviz, Energy Analytix, Facility Analytix and 8 more | 2024-11-21 | 9.8 Critical |
A specially crafted communication packet sent to the affected devices could allow remote code execution and a denial-of-service condition due to a deserialization vulnerability. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server version 10.96 and prior; ICONICS GenBroker32 version 9.5 and prior. | ||||
CVE-2016-2289 | 1 Iconics | 1 Webhmi | 2024-11-21 | N/A |
Directory traversal vulnerability in ICONICS WebHMI 9 and earlier allows remote attackers to read configuration files, and consequently discover password hashes, via unspecified vectors. | ||||
CVE-2014-0758 | 1 Iconics | 1 Genesis32 | 2024-11-21 | N/A |
An ActiveX control in GenLaunch.htm in ICONICS GENESIS32 8.0, 8.02, 8.04, and 8.05 allows remote attackers to execute arbitrary programs via a crafted HTML document. | ||||
CVE-2012-3018 | 1 Iconics | 2 Bizviz, Genesis32 | 2024-11-21 | N/A |
The lockout-recovery feature in the Security Configurator component in ICONICS GENESIS32 9.22 and earlier and BizViz 9.22 and earlier uses an improper encryption algorithm for generation of an authentication code, which allows local users to bypass intended access restrictions and obtain administrative access by predicting a challenge response. | ||||
CVE-2011-5089 | 1 Iconics | 2 Bizviz, Genesis32 | 2024-11-21 | N/A |
Buffer overflow in the Security Login ActiveX controls in ICONICS GENESIS32 8.05, 9.0, 9.1, and 9.2 and BizViz 8.05, 9.0, 9.1, and 9.2 allows remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via a long password. | ||||
CVE-2011-5088 | 1 Iconics | 2 Bizviz, Genesis32 | 2024-11-21 | N/A |
The GENESIS32 IcoSetServer ActiveX control in ICONICS GENESIS32 9.21 and BizViz 9.21 configures the trusted zone on the basis of user input, which allows remote attackers to execute arbitrary code via a crafted web site, related to a "Workbench32/WebHMI component SetTrustedZone Policy vulnerability." | ||||
CVE-2011-2089 | 1 Iconics | 2 Bizviz, Genesis32 | 2024-11-21 | N/A |
Stack-based buffer overflow in the SetActiveXGUID method in the VersionInfo ActiveX control in GenVersion.dll 8.0.138.0 in the WebHMI subsystem in ICONICS BizViz 9.x before 9.22 and GENESIS32 9.x before 9.22 allows remote attackers to execute arbitrary code via a long string in the argument. NOTE: some of these details are obtained from third party information. | ||||
CVE-2006-6488 | 1 Iconics | 1 Dialog Wrapper Module Activex Control | 2024-11-21 | N/A |
Stack-based buffer overflow in the DoModal function in the Dialog Wrapper Module ActiveX control (DlgWrapper.dll) before 8.4.166.0, as used by ICONICS OPC Enabled Gauge, Switch, and Vessel ActiveX, allows remote attackers to execute arbitrary code via a long (1) FileName or (2) Filter argument. | ||||
CVE-2024-7587 | 2 Iconics, Mitsubishielectric | 2 Genesis64, Mc Works64 | 2024-11-06 | 7.8 High |
Incorrect Default Permissions vulnerability in GenBroker32, which is included in the installers for ICONICS GENESIS64 version 10.97.3 and prior, Mitsubishi Electric GENESIS64 version 10.97.3 and prior and Mitsubishi Electric MC Works64 all versions allows a local authenticated attacker to disclose or tamper with confidential information and data contained in the products, or cause a denial of service (DoS) condition on the products, by accessing a folder with incorrect permissions, when GenBroker32 is installed on the same PC as GENESIS64 or MC Works64. |