Search Results (357821 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2022-41636 1 Haascnc 1 Haas Controller 2025-04-16 9.1 Critical
Communication traffic involving "Ethernet Q Commands" service of Haas Controller version 100.20.000.1110 is transmitted in cleartext. This allows an attacker to obtain sensitive information being passed to and from the controller.
CVE-2022-3228 1 Hosteng 2 H0-ecom100, H0-ecom100 Firmware 2025-04-16 6.5 Medium
Using custom code, an attacker can write into name or description fields larger than the appropriate buffer size causing a stack-based buffer overflow on Host Engineering H0-ECOM100 Communications Module Firmware versions v5.0.155 and prior. This may allow an attacker to crash the affected device or cause it to become unresponsive.
CVE-2022-38142 1 Deltaww 1 Infrasuite Device Master 2025-04-16 9.8 Critical
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-Gateway service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization.
CVE-2022-41657 1 Deltaww 1 Infrasuite Device Master 2025-04-16 9.8 Critical
Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior allow attacker provided data already serialized into memory to be used in file operation application programmable interfaces (APIs). This could create arbitrary files, which could be used in API operations and could ultimately result in remote code execution.
CVE-2022-41772 1 Deltaww 1 Infrasuite Device Master 2025-04-16 9.8 Critical
Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior mishandle .ZIP archives containing characters used in path traversal. This path traversal could result in remote code execution.
CVE-2022-40202 1 Deltaww 1 Infrasuite Device Master 2025-04-16 9.8 Critical
The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution.
CVE-2022-41688 1 Deltaww 1 Infrasuite Device Master 2025-04-16 9.8 Critical
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lack proper authentication for functions that create and modify user groups. An attacker could provide malicious serialized objects that could run these functions without authentication to create a new user and add them to the administrator group.
CVE-2022-41776 1 Deltaww 1 Infrasuite Device Master 2025-04-16 7.5 High
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to trigger the WriteConfiguration method, which could allow an attacker to provide new values for user configuration files such as UserListInfo.xml. This could lead to the changing of administrative passwords.
CVE-2022-41629 1 Deltaww 1 Infrasuite Device Master 2025-04-16 7.5 High
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to access the aprunning endpoint, which could allow an attacker to retrieve any file from the “RunningConfigs” directory. The attacker could then view and modify configuration files such as UserListInfo.xml, which would allow them to see existing administrative passwords.
CVE-2022-3181 1 Trihedral 1 Vtscada 2025-04-16 7.5 High
An Improper Input Validation vulnerability exists in Trihedral VTScada version 12.0.38 and prior. A specifically malformed HTTP request could cause the affected VTScada to crash. Both local area network (LAN)-only and internet facing systems are affected.
CVE-2022-3090 1 Redlion 1 Crimson 2025-04-16 7.5 High
Red Lion Controls Crimson 3.0 versions 707.000 and prior, Crimson 3.1 versions 3126.001 and prior, and Crimson 3.2 versions 3.2.0044.0 and prior are vulnerable to path traversal. When attempting to open a file using a specific path, the user's password hash is sent to an arbitrary host. This could allow an attacker to obtain user credential hashes.
CVE-2022-2791 1 Emerson 1 Proficy 2025-04-16 5.9 Medium
Emerson Electric's Proficy Machine Edition Version 9.00 and prior is vulnerable to CWE-434 Unrestricted Upload of File with Dangerous Type, and will upload any file written into the PLC logic folder to the connected PLC.
CVE-2019-18265 1 Digitalalertsystems 10 Dasdec I, Dasdec I Firmware, Dasdec Ii and 7 more 2025-04-16 4.7 Medium
Digital Alert Systems’ DASDEC software prior to version 4.1 contains a cross-site scripting (XSS) vulnerability that allows remote attackers to inject arbitrary web script or HTML via the SSH username, username field of the login page, or via the HTTP host header. The injected content is stored in logs and rendered when viewed in the web application.
CVE-2022-40204 1 Digitalalertsystems 10 Dasdec I, Dasdec I Firmware, Dasdec Ii and 7 more 2025-04-16 4.1 Medium
A cross-site scripting (XSS) vulnerability exists in all current versions of Digital Alert Systems DASDEC software via the Host Header in undisclosed pages after login.
CVE-2022-2969 1 Deltaww 1 Dialink 2025-04-16 8.1 High
Delta Industrial Automation DIALink versions prior to v1.5.0.0 Beta 4 uses an external input to construct a pathname intended to identify a file or directory located underneath a restricted parent directory. However, the software does not properly neutralize special elements within the pathname, which can cause the pathname to resolve to a location outside of the restricted directory.
CVE-2022-2641 1 Hornerautomation 2 Rcc972, Rcc972 Firmware 2025-04-16 9.8 Critical
Horner Automation’s RCC 972 with firmware version 15.40 has a static encryption key on the device. This could allow an attacker to perform unauthorized changes to the device, remotely execute arbitrary code, or cause a denial-of-service condition.
CVE-2022-2640 1 Hornerautomation 2 Rcc972, Rcc972 Firmware 2025-04-16 7.5 High
The Config-files of Horner Automation’s RCC 972 with firmware version 15.40 are encrypted with weak XOR encryption vulnerable to reverse engineering. This could allow an attacker to obtain credentials to run services such as File Transfer Protocol (FTP) and Hypertext Transfer Protocol (HTTP).
CVE-2022-2642 1 Hornerautomation 2 Rcc972, Rcc972 Firmware 2025-04-16 7.5 High
Horner Automation’s RCC 972 firmware version 15.40 contains global variables. This could allow an attacker to read out sensitive values and variable keys from the device.
CVE-2022-41653 1 Daikinlatam 2 Svmpc1, Svmpc2 2025-04-16 9.8 Critical
Daikin SVMPC1 version 2.1.22 and prior and SVMPC2 version 1.2.3 and prior are vulnerable to an attacker obtaining user login credentials and control the system.
CVE-2022-38355 1 Daikinlatam 2 Svmpc1, Svmpc2 2025-04-16 7.5 High
Daikin SVMPC1 version 2.1.22 and prior and SVMPC2 version 1.2.3 and prior are vulnerable to attackers with access to the local area network (LAN) to disclose sensitive information stored by the affected product without requiring authentication.