Filtered by vendor Rittal Subscriptions
Filtered by product Cmc Pu Iii 7030.000 Firmware Subscriptions
Total 3 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2021-40223 1 Rittal 2 Cmc Pu Iii 7030.000, Cmc Pu Iii 7030.000 Firmware 2024-11-21 5.4 Medium
Rittal CMC PU III Web management (version V3.11.00_2) fails to sanitize user input on several parameters of the configuration (User Configuration dialog, Task Configuration dialog and set logging filter dialog). This allows an attacker to backdoor the device with HTML and browser-interpreted content (such as JavaScript or other client-side scripts). The XSS payload will be triggered when the user accesses some specific sections of the application.
CVE-2021-40222 1 Rittal 2 Cmc Pu Iii 7030.000, Cmc Pu Iii 7030.000 Firmware 2024-11-21 7.2 High
Rittal CMC PU III Web management Version affected: V3.11.00_2. Version fixed: V3.17.10 is affected by a remote code execution vulnerablity. It is possible to introduce shell code to create a reverse shell in the PU-Hostname field of the TCP/IP Configuration dialog. Web application fails to sanitize user input on Network TCP/IP configuration page. This allows the attacker to inject commands as root on the device which will be executed once the data is received.
CVE-2019-19393 1 Rittal 2 Cmc Pu Iii 7030.000, Cmc Pu Iii 7030.000 Firmware 2024-11-21 6.1 Medium
The Web application on Rittal CMC PU III 7030.000 V3.00 V3.11.00_2 to V3.15.70_4 devices fails to sanitize user input on the system configurations page. This allows an attacker to backdoor the device with HTML and browser-interpreted content (such as JavaScript or other client-side scripts) as the content is always displayed after and before login. Persistent XSS allows an attacker to modify displayed content or to change the victim's information. Successful exploitation requires access to the web management interface, either with valid credentials or a hijacked session.