Filtered by vendor Rittal Subscriptions
Total 12 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2022-40633 1 Rittal 2 Cmc Iii, Cmc Iii Firmware 2024-11-21 4.6 Medium
A malicious actor can clone access cards used to open control cabinets secured with Rittal CMC III locks.
CVE-2021-40223 1 Rittal 2 Cmc Pu Iii 7030.000, Cmc Pu Iii 7030.000 Firmware 2024-11-21 5.4 Medium
Rittal CMC PU III Web management (version V3.11.00_2) fails to sanitize user input on several parameters of the configuration (User Configuration dialog, Task Configuration dialog and set logging filter dialog). This allows an attacker to backdoor the device with HTML and browser-interpreted content (such as JavaScript or other client-side scripts). The XSS payload will be triggered when the user accesses some specific sections of the application.
CVE-2021-40222 1 Rittal 2 Cmc Pu Iii 7030.000, Cmc Pu Iii 7030.000 Firmware 2024-11-21 7.2 High
Rittal CMC PU III Web management Version affected: V3.11.00_2. Version fixed: V3.17.10 is affected by a remote code execution vulnerablity. It is possible to introduce shell code to create a reverse shell in the PU-Hostname field of the TCP/IP Configuration dialog. Web application fails to sanitize user input on Network TCP/IP configuration page. This allows the attacker to inject commands as root on the device which will be executed once the data is received.
CVE-2020-11956 1 Rittal 9 Cmc Iii Pu 7030.000, Cmc Iii Pu 7030.000 Firmware, Cmciii-pu-9333e0fb and 6 more 2024-11-21 9.8 Critical
An issue was discovered on Rittal PDU-3C002DEC through 5.17.10 and CMCIII-PU-9333E0FB through 3.17.10 devices. There is a least privilege violation.
CVE-2020-11955 1 Rittal 9 Cmc Iii Pu 7030.000, Cmc Iii Pu 7030.000 Firmware, Cmciii-pu-9333e0fb and 6 more 2024-11-21 8.8 High
An issue was discovered on Rittal PDU-3C002DEC through 5.15.70 and CMCIII-PU-9333E0FB through 3.15.70 devices. There are insecure permissions.
CVE-2020-11953 1 Rittal 9 Cmc Iii Pu 7030.000, Cmc Iii Pu 7030.000 Firmware, Cmciii-pu-9333e0fb and 6 more 2024-11-21 8.8 High
An issue was discovered on Rittal PDU-3C002DEC through 5.15.40 and CMCIII-PU-9333E0FB through 3.15.70_4 devices. Attackers can execute code.
CVE-2020-11952 1 Rittal 9 Cmc Iii Pu 7030.000, Cmc Iii Pu 7030.000 Firmware, Cmciii-pu-9333e0fb and 6 more 2024-11-21 6.2 Medium
An issue was discovered on Rittal PDU-3C002DEC through 5.17.10 and CMCIII-PU-9333E0FB through 3.17.10 devices. Attackers can bypass the CLI menu.
CVE-2020-11951 1 Rittal 9 Cmc Iii Pu 7030.000, Cmc Iii Pu 7030.000 Firmware, Cmciii-pu-9333e0fb and 6 more 2024-11-21 9.8 Critical
An issue was discovered on Rittal PDU-3C002DEC through 5.17.10 and CMCIII-PU-9333E0FB through 3.17.10 devices. There is a Backdoor root account.
CVE-2019-19393 1 Rittal 2 Cmc Pu Iii 7030.000, Cmc Pu Iii 7030.000 Firmware 2024-11-21 6.1 Medium
The Web application on Rittal CMC PU III 7030.000 V3.00 V3.11.00_2 to V3.15.70_4 devices fails to sanitize user input on the system configurations page. This allows an attacker to backdoor the device with HTML and browser-interpreted content (such as JavaScript or other client-side scripts) as the content is always displayed after and before login. Persistent XSS allows an attacker to modify displayed content or to change the victim's information. Successful exploitation requires access to the web management interface, either with valid credentials or a hijacked session.
CVE-2019-13553 2 Carel, Rittal 2 Pcoweb Firmware, Chiller Sk 3232 2024-11-21 9.8 Critical
Rittal Chiller SK 3232-Series web interface as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4. The authentication mechanism on affected systems is configured using hard-coded credentials. These credentials could allow attackers to influence the primary operations of the affected systems, namely turning the cooling unit on and off and setting the temperature set point.
CVE-2019-13549 2 Carel, Rittal 2 Pcoweb Firmware, Chiller Sk 3232 2024-11-21 7.5 High
Rittal Chiller SK 3232-Series web interface as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4. The authentication mechanism on affected systems does not provide a sufficient level of protection against unauthorized configuration changes. Primary operations, namely turning the cooling unit on and off and setting the temperature set point, can be modified without authentication.
CVE-2024-47945 2 Rittal, Rittal Gmbh And Co.kg 5 Cmc Iii Processing Units, Cmc Iii Processing Units Firmware, Iot Interface and 2 more 2024-10-21 9.1 Critical
The devices are vulnerable to session hijacking due to insufficient entropy in its session ID generation algorithm. The session IDs are predictable, with only 32,768 possible values per user, which allows attackers to pre-generate valid session IDs, leading to unauthorized access to user sessions. This is not only due to the use of an (insecure) rand() function call but also because of missing initialization via srand(). As a result only the PIDs are effectively used as seed.