Filtered by vendor Emerson Subscriptions
Filtered by product Controlwave Micro Subscriptions
Total 2 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2022-30262 1 Emerson 4 Controlwave Micro, Controlwave Micro Firmware, Controlwave Pac and 1 more 2024-11-21 7.8 High
The Emerson ControlWave 'Next Generation' RTUs through 2022-05-02 mishandle firmware integrity. They utilize the BSAP-IP protocol to transmit firmware updates. Firmware updates are supplied as CAB archive files containing a binary firmware image. In all cases, firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks.
CVE-2018-5452 1 Emerson 2 Controlwave Micro, Controlwave Micro Firmware 2024-11-21 7.5 High
A Stack-based Buffer Overflow issue was discovered in Emerson Process Management ControlWave Micro Process Automation Controller: ControlWave Micro [ProConOS v.4.01.280] firmware: CWM v.05.78.00 and prior. A stack-based buffer overflow vulnerability caused by sending crafted packets on Port 20547 could force the PLC to change its state into halt mode.