The Emerson ControlWave 'Next Generation' RTUs through 2022-05-02 mishandle firmware integrity. They utilize the BSAP-IP protocol to transmit firmware updates. Firmware updates are supplied as CAB archive files containing a binary firmware image. In all cases, firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks.
Metrics
Affected Vendors & Products
References
History
No history.
MITRE
Status: PUBLISHED
Assigner: mitre
Published: 2022-08-17T14:27:08
Updated: 2024-08-03T06:40:47.822Z
Reserved: 2022-05-04T00:00:00
Link: CVE-2022-30262
Vulnrichment
No data.
NVD
Status : Modified
Published: 2022-08-17T15:15:08.260
Modified: 2024-11-21T07:02:27.627
Link: CVE-2022-30262
Redhat
No data.