The Emerson ControlWave 'Next Generation' RTUs through 2022-05-02 mishandle firmware integrity. They utilize the BSAP-IP protocol to transmit firmware updates. Firmware updates are supplied as CAB archive files containing a binary firmware image. In all cases, firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks.
Metrics
Affected Vendors & Products
Advisories
Source | ID | Title |
---|---|---|
![]() |
EUVD-2022-52222 | The Emerson ControlWave 'Next Generation' RTUs through 2022-05-02 mishandle firmware integrity. They utilize the BSAP-IP protocol to transmit firmware updates. Firmware updates are supplied as CAB archive files containing a binary firmware image. In all cases, firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. |
Fixes
Solution
No solution given by the vendor.
Workaround
No workaround given by the vendor.
References
History
No history.

Status: PUBLISHED
Assigner: mitre
Published:
Updated: 2024-08-03T06:40:47.822Z
Reserved: 2022-05-04T00:00:00
Link: CVE-2022-30262

No data.

Status : Modified
Published: 2022-08-17T15:15:08.260
Modified: 2024-11-21T07:02:27.627
Link: CVE-2022-30262

No data.

No data.