Filtered by vendor Opto22 Subscriptions
Total 13 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2023-40710 1 Opto22 2 Snap Pac S1, Snap Pac S1 Firmware 2024-11-21 6.8 Medium
An adversary could cause a continuous restart loop to the entire device by sending a large quantity of HTTP GET requests if the controller has the built-in web server enabled but does not have the built-in web server completely set up and configured for the SNAP PAC S1 Firmware version R10.3b
CVE-2023-40709 1 Opto22 2 Snap Pac S1, Snap Pac S1 Firmware 2024-11-21 6.8 Medium
An adversary could crash the entire device by sending a large quantity of ICMP requests if the controller has the built-in web server enabled but does not have the built-in web server completely set up and configured for the SNAP PAC S1 Firmware version R10.3b
CVE-2023-40708 1 Opto22 2 Snap Pac S1, Snap Pac S1 Firmware 2024-11-21 5.8 Medium
The File Transfer Protocol (FTP) port is open by default in the SNAP PAC S1 Firmware version R10.3b. This could allow an adversary to access some device files.
CVE-2023-40707 1 Opto22 2 Snap Pac S1, Snap Pac S1 Firmware 2024-11-21 8.6 High
There are no requirements for setting a complex password in the built-in web server of the SNAP PAC S1 Firmware version R10.3b, which could allow for a successful brute force attack if users don't set up complex credentials.
CVE-2023-40706 1 Opto22 2 Snap Pac S1, Snap Pac S1 Firmware 2024-11-21 8.6 High
There is no limit on the number of login attempts in the web server for the SNAP PAC S1 Firmware version R10.3b. This could allow for a brute-force attack on the built-in web server login.
CVE-2020-12046 1 Opto22 1 Softpac Project 2024-11-21 5.7 Medium
Opto 22 SoftPAC Project Version 9.6 and prior. SoftPAC’s firmware files’ signatures are not verified upon firmware update. This allows an attacker to replace legitimate firmware files with malicious files.
CVE-2020-12042 1 Opto22 1 Softpac Project 2024-11-21 6.5 Medium
Opto 22 SoftPAC Project Version 9.6 and prior. Paths specified within the zip files used to update the SoftPAC firmware are not sanitized. As a result, an attacker with user privileges can gain arbitrary file write access with system access.
CVE-2020-10620 1 Opto22 1 Softpac Project 2024-11-21 9.8 Critical
Opto 22 SoftPAC Project Version 9.6 and prior. SoftPAC communication does not include any credentials. This allows an attacker with network access to directly communicate with SoftPAC, including, for example, stopping the service remotely.
CVE-2020-10616 1 Opto22 1 Softpac Project 2024-11-21 8.8 High
Opto 22 SoftPAC Project Version 9.6 and prior. SoftPAC does not specify the path of multiple imported .dll files. Therefore, an attacker can replace them and execute code whenever the service starts.
CVE-2020-10612 1 Opto22 1 Softpac Project 2024-11-21 9.1 Critical
Opto 22 SoftPAC Project Version 9.6 and prior. SoftPACAgent communicates with SoftPACMonitor over network Port 22000. However, this port is open without any restrictions. This allows an attacker with network access to control the SoftPACAgent service including updating SoftPAC firmware, starting or stopping service, or writing to certain registry values.
CVE-2018-14807 1 Opto22 1 Pac Control 2024-11-21 9.8 Critical
A stack-based buffer overflow vulnerability in Opto 22 PAC Control Basic and PAC Control Professional versions R10.0a and prior may allow remote code execution.
CVE-2015-1007 1 Opto22 4 Optodatalink, Optoopcserver, Pac Display and 1 more 2024-11-21 N/A
A specially crafted configuration file could be used to cause a stack-based buffer overflow condition in the OPCTest.exe, which may allow remote code execution on Opto 22 PAC Project Professional versions prior to R9.4008, PAC Project Basic versions prior to R9.4008, PAC Display Basic versions prior to R9.4g, PAC Display Professional versions prior to R9.4g, OptoOPCServer version R9.4c and prior that were installed by PAC Project installer, versions prior to R9.4008, and OptoDataLink version R9.4d and prior that were installed by PAC Project installer, versions prior to R9.4008. Opto 22 suggests upgrading to the new product version as soon as possible.
CVE-2015-1006 1 Opto22 4 Optodatalink, Optoopcserver, Pac Display and 1 more 2024-11-21 N/A
A vulnerable file in Opto 22 PAC Project Professional versions prior to R9.4006, PAC Project Basic versions prior to R9.4006, PAC Display Basic versions prior to R9.4f, PAC Display Professional versions prior to R9.4f, OptoOPCServer versions prior to R9.4c, and OptoDataLink version R9.4d and prior versions that were installed by PAC Project installer, versions prior to R9.4006, is susceptible to a heap-based buffer overflow condition that may allow remote code execution on the target system. Opto 22 suggests upgrading to the new product version as soon as possible.