Filtered by vendor Progea
Subscriptions
Total
8 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2017-14019 | 1 Progea | 1 Movicon | 2024-11-21 | N/A |
An Unquoted Search Path or Element issue was discovered in Progea Movicon Version 11.5.1181 and prior. An unquoted search path or element vulnerability has been identified, which may allow an authorized local user to insert arbitrary code into the unquoted service path and escalate his or her privileges. | ||||
CVE-2017-14017 | 1 Progea | 1 Movicon | 2024-11-21 | N/A |
An Uncontrolled Search Path Element issue was discovered in Progea Movicon Version 11.5.1181 and prior. An uncontrolled search path element vulnerability has been identified, which may allow a remote attacker without privileges to execute arbitrary code in the form of a malicious DLL file. | ||||
CVE-2014-0778 | 1 Progea | 1 Movicon | 2024-11-21 | N/A |
The TCPUploader module in Progea Movicon 11.4 before 11.4.1150 allows remote attackers to obtain potentially sensitive version information via network traffic to TCP port 10651. | ||||
CVE-2012-1804 | 1 Progea | 1 Movicon | 2024-11-21 | N/A |
The OPC server in Progea Movicon before 11.3 allows remote attackers to cause a denial of service (out-of-bounds read and memory corruption) via a crafted HTTP request. | ||||
CVE-2011-3499 | 1 Progea | 1 Movicon Powerhmi | 2024-11-21 | N/A |
Progea Movicon / PowerHMI 11.2.1085 and earlier allows remote attackers to cause a denial of service (memory corruption and crash) and possibly execute arbitrary code via an EIDP packet with a large size field, which writes a zero byte to an arbitrary memory location. | ||||
CVE-2011-3498 | 1 Progea | 1 Movicon Powerhmi | 2024-11-21 | N/A |
Heap-based buffer overflow in Progea Movicon / PowerHMI 11.2.1085 and earlier allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via a long request. | ||||
CVE-2011-3491 | 1 Progea | 1 Movicon Powerhmi | 2024-11-21 | N/A |
Heap-based buffer overflow in Progea Movicon / PowerHMI 11.2.1085 and earlier allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via a negative Content-Length field. | ||||
CVE-2011-2963 | 1 Progea | 1 Movicon | 2024-11-21 | N/A |
TCPUploadServer.exe in Progea Movicon 11.2 before Build 1084 does not require authentication for critical functions, which allows remote attackers to obtain sensitive information, delete files, execute arbitrary programs, or cause a denial of service (crash) via a crafted packet to TCP port 10651. |