The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution.
Metrics
Affected Vendors & Products
References
Link | Providers |
---|---|
https://www.cisa.gov/uscert/ics/advisories/icsa-22-298-07 |
History
No history.
MITRE
Status: PUBLISHED
Assigner: icscert
Published: 2022-10-31T19:35:08.629Z
Updated: 2024-08-03T12:14:39.961Z
Reserved: 2022-09-29T14:08:03.199Z
Link: CVE-2022-40202
Vulnrichment
No data.
NVD
Status : Modified
Published: 2022-10-31T20:15:12.987
Modified: 2024-11-21T07:21:03.447
Link: CVE-2022-40202
Redhat
No data.