An improper resource shutdown or release vulnerability has been identified in the Click Plus C2-03CPU-2 device running firmware version 3.60. The vulnerability allows an unauthenticated attacker to perform a denial-of-service attack by exhausting all available device sessions of the Click Programming Software.
Fixes

Solution

AutomationDirect recommends that users update CLICK PLUS and firmware to V3.80. https://www.automationdirect.com/support/software-downloads If the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed: * Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure. * Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication. * Access Control – Restrict both physical and logical access to authorized personnel only. * Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software. * Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts. * Logging & Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity. * Backup & Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident. * Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.


Workaround

No workaround given by the vendor.

History

Tue, 23 Sep 2025 22:30:00 +0000

Type Values Removed Values Added
Description An improper resource shutdown or release vulnerability has been identified in the Click Plus C2-03CPU-2 device running firmware version 3.60. The vulnerability allows an unauthenticated attacker to perform a denial-of-service attack by exhausting all available device sessions of the Click Programming Software.
Title AutomationDirect CLICK PLUS Improper Resource Shutdown or Release
Weaknesses CWE-404
References
Metrics cvssV3_1

{'score': 5.9, 'vector': 'CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H'}

cvssV4_0

{'score': 8.2, 'vector': 'CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N'}


cve-icon MITRE

Status: PUBLISHED

Assigner: icscert

Published:

Updated: 2025-09-23T22:21:06.164Z

Reserved: 2025-09-16T20:09:26.651Z

Link: CVE-2025-58473

cve-icon Vulnrichment

No data.

cve-icon NVD

Status : Received

Published: 2025-09-23T23:15:31.103

Modified: 2025-09-23T23:15:31.103

Link: CVE-2025-58473

cve-icon Redhat

No data.

cve-icon OpenCVE Enrichment