Technical impact
The flaw is an incorrect authorization bug that allows an attacker who can interact with the protection relay to perform actions outside the intended scope. With this vulnerability, an adversary could change protection settings, override timers, or disable protective functions, compromising the integrity of the protection system. The weakness is categorized as CWE‑863, a classic access control flaw where the system fails to validate privileges before allowing critical operations.
Affected Systems
Affected products are ABB’s Relion Protection Relays across the 615, 620, and REX series, as well as the Substation Merging Unit SMU615. Specific models include REX610, RE_611, RBX615, REF615, REF615R, RER615, REC615, REX615, the 615 series (IEC, CN, ANSI), RER620, 620 series (ANSI, IEC/CN), REX640, and SMU615. The vulnerable firmware releases span numerous software versions: for example, REX610 V1.0‑1.2, RE_611 V1.0‑2.0, RBX615 V1.0‑2.0, REF615 V4.1, REF615R V4.0 and FP1, RER615 V1.0‑2.0, REC615 V1.0‑3.0, REX615 across PCL1‑PCL3 and SW 6.0‑6.2, the 615 series from 3.1 to 5.0 FP1, the 620 series from 2.0 to 2.0 FP1, REX640 across multiple PCL versions, and SMU615 V1.0.
Risk and Exploitability
The CVSS score of 7.5 indicates a high severity that can result in compromise of critical protection logic. EPSS data is not disclosed, and the flaw is not listed in the CISA KEV catalog, suggesting that while the technical risk is significant, there is no current evidence of active exploitation. The likely attack vector depends on the relay’s management interface; if it is exposed to a network, a remote attacker could gain unauthorized control; if local, an insider or a device with physical connection could exploit it. In both scenarios, successful exploitation could degrade system availability or facilitate broader control of the power infrastructure. No additional prerequisites are specified, implying that basic network reachability or physical access may suffice to trigger the flaw.