Filtered by vendor Rockwellautomation Subscriptions
Total 280 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2020-25184 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2024-11-21 7.8 High
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x stores the password in plaintext in a file that is in the same directory as the executable file. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification. A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure.
CVE-2020-25182 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2024-11-21 6.7 Medium
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems.
CVE-2020-25180 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2024-11-21 5.3 Medium
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.
CVE-2020-25178 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2024-11-21 7.5 High
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.
CVE-2020-25176 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2024-11-21 9.1 Critical
Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution.
CVE-2020-14516 1 Rockwellautomation 1 Factorytalk Services Platform 2024-11-21 10.0 Critical
In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly.
CVE-2020-14504 1 Rockwellautomation 4 1734-aentr Point I\/o Dual Port Network Adaptor Series B, 1734-aentr Point I\/o Dual Port Network Adaptor Series B Firmware, 1734-aentr Point I\/o Dual Port Network Adaptor Series C and 1 more 2024-11-21 5.3 Medium
The web interface of the 1734-AENTR communication module mishandles authentication for HTTP POST requests. A remote, unauthenticated attacker can send a crafted request that may allow for modification of the configuration settings.
CVE-2020-14502 1 Rockwellautomation 4 1734-aentr Point I\/o Dual Port Network Adaptor Series B, 1734-aentr Point I\/o Dual Port Network Adaptor Series B Firmware, 1734-aentr Point I\/o Dual Port Network Adaptor Series C and 1 more 2024-11-21 6.1 Medium
The web interface of the 1734-AENTR communication module is vulnerable to stored XSS. A remote, unauthenticated attacker could store a malicious script within the web interface that, when executed, could modify some string values on the homepage of the web interface.
CVE-2020-14481 1 Rockwellautomation 1 Factorytalk View 2024-11-21 7.8 High
The DeskLock tool provided with FactoryTalk View SE uses a weak encryption algorithm that may allow a local, authenticated attacker to decipher user credentials, including the Windows user or Windows DeskLock passwords. If the compromised user has an administrative account, an attacker could gain full access to the user’s operating system and certain components of FactoryTalk View SE.
CVE-2020-14480 1 Rockwellautomation 1 Factorytalk View 2024-11-21 5.5 Medium
Due to usernames/passwords being stored in plaintext in Random Access Memory (RAM), a local, authenticated attacker could gain access to certain credentials, including Windows Logon credentials.
CVE-2020-14478 1 Rockwellautomation 1 Factorytalk Services Platform 2024-11-21 7.1 High
A local, authenticated attacker could use an XML External Entity (XXE) attack to exploit weakly configured XML files to access local or remote content. A successful exploit could potentially cause a denial-of-service condition and allow the attacker to arbitrarily read any local file via system-level services.
CVE-2020-13573 1 Rockwellautomation 1 Rslinx 2024-11-21 7.5 High
A denial-of-service vulnerability exists in the Ethernet/IP server functionality of Rockwell Automation RSLinx Classic 2.57.00.14 CPR 9 SR 3. A specially crafted network request can lead to a denial of service. An attacker can send a sequence of malicious packets to trigger this vulnerability.
CVE-2020-12038 1 Rockwellautomation 5 Eds Subsystem, Rslinx, Rslinx Enterprise and 2 more 2024-11-21 5.5 Medium
Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable. A memory corruption vulnerability exists in the algorithm that matches square brackets in the EDS subsystem. This may allow an attacker to craft specialized EDS files to crash the EDSParser COM object, leading to denial-of-service conditions.
CVE-2020-12034 1 Rockwellautomation 5 Eds Subsystem, Rslinx, Rslinx Enterprise and 2 more 2024-11-21 8.2 High
Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable.The EDS subsystem does not provide adequate input sanitation, which may allow an attacker to craft specialized EDS files to inject SQL queries and manipulate the database storing the EDS files. This can lead to denial-of-service conditions.
CVE-2020-12033 1 Rockwellautomation 1 Factorytalk Services Platform 2024-11-21 8.8 High
In Rockwell Automation FactoryTalk Services Platform, all versions, the redundancy host service (RdcyHost.exe) does not validate supplied identifiers, which could allow an unauthenticated, adjacent attacker to execute remote COM objects with elevated privileges.
CVE-2020-12031 1 Rockwellautomation 1 Factorytalk View 2024-11-21 7.5 High
In all versions of FactoryTalk View SE, after bypassing memory corruption mechanisms found in the operating system, a local, authenticated attacker may corrupt the associated memory space allowing for arbitrary code execution. Rockwell Automation recommends applying patch 1126290. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
CVE-2020-12029 1 Rockwellautomation 1 Factorytalk View 2024-11-21 9 Critical
All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
CVE-2020-12028 1 Rockwellautomation 1 Factorytalk View 2024-11-21 7.3 High
In all versions of FactoryTalk View SEA remote, an authenticated attacker may be able to utilize certain handlers to interact with the data on the remote endpoint since those handlers do not enforce appropriate permissions. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.
CVE-2020-12027 1 Rockwellautomation 1 Factorytalk View 2024-11-21 4.3 Medium
All versions of FactoryTalk View SE disclose the hostnames and file paths for certain files within the system. A remote, authenticated attacker may be able to leverage this information for reconnaissance efforts. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.
CVE-2020-12025 1 Rockwellautomation 1 Studio 5000 Logix Designer 2024-11-21 3.3 Low
Rockwell Automation Logix Designer Studio 5000 Versions 32.00, 32.01, and 32.02 vulnerable to an xml external entity (XXE) vulnerability, which may allow an attacker to view hostnames or other resources from the program.